16

Power Requirements

FT 5000 Control Module

The following sections describe the power requirements for the FT 5000 Control

Module.

Control Module Power Requirements

FT 5000 Control Modules require a +3.3 VDC power source with sufficient

current to power the control module in all modes of operation.
The supply current requirements for the FT 5000 Control Modules are outlined

in Table 7, including typical requirements for the different operating states of

the FT 5000 Smart Transceiver at various system clock rates.

Table 7. FT 5000 Current Requirements

Active

SysClk

Typical

Maximum

Receive Current

5 MHz

9 mA

15 mA

10 MHz

9 mA

15 mA

20 MHz

15 mA

23 mA

40 MHz

23 mA

33 mA

80 MHz

38 mA

52 mA

Transmit Current 5 – 80 MHz

Receive Current

+ 15 mA

Receive Current

+ 18 mA

The FT 5000 Control Module requires a 3.3 V nominal power supply (3.0 V to 3.6

V range). The current requirements assume no load on digital I/O pins, and that

the I/O lines are not switching. In addition, the current consumption in transmit

mode represents a peak value rather than a continuous usage value because an

FT 5000 Smart Transceiver does not typically transmit data continuously.
Note that the stated current requirements do not include the requirements for

performing reads or writes to the external memory (the two-wire serial

EEPROM), which typically add 1 to 2 mA. When not in use, the EEPROM

typically requires only 2 μA.

Neuron 3150 Control Modules

The following sections describe the power requirements for the Neuron 3150

Control Modules.

Control Module Power Requirements

Twisted Pair Control Modules require a +5 VDC power source with sufficient

current to power the control module in all modes of operation.