beautypg.com

Mechanical footprint – Echelon LonWorks Twisted Pair Control Module User Manual

Page 17

background image

LonWorks Twisted Pair Control Module User's Guide

9

Mechanical Footprint

The Neuron 3150 Twisted Pair Control Modules share a common footprint and

connectors as shown in Figure 5 on page 10. The most common control module

mounting scenario uses socket strips on the application electronics board which

connect with P1 and P2 as shown in Figure 6 and Figure 7 on page 11.

Example vendor information for socket strips that mate with the 0.025 inch (0.64

mm) square header posts of P1 and P2 are listed in Table 6 on page 11.
If necessary, taller socket strips can be used to gain more clearance between the

control module and the application board. Decisions about component placement

on the application electronics board must also consider the electromagnetic

interference (EMI) and electrostatic discharge (ESD) issues discussed in Chapter

5, Design Issues, on page 27.
Figure 6 and Figure 7 show the maximum height of parts on both sides of the

control modules. Application designs using the transformer-isolated twisted pair

transceivers should maintain a minimum of 0.15 inch (3.81 mm) clearance from

P2 pins and traces on the network side of the transformer to achieve the

minimum isolation specified for these modules. Refer to EMI Design Issues on

page 28 and Neuron 3150 Control Module Keepout Areas on page 31 for isolation

requirements.
Three plated mounting holes that accept No. 6 (3.5 mm) mounting screws are

electrically connected to the control module ground plane. When the 0.025 inch

(0.64 mm) square posts of P1 and P2 are inserted into the sockets they provide

enough holding strength (3 oz (85 g)/pin) to secure the control module against

shock and vibration to the operating limits of the components on the control

module. However, at least one metal standoff and fastening screw located at the

mounting hole near the P2 connector is recommended to meet EMI limits and for

ESD protection (see Chapter 5).
For the TP/FT-10 control modules, the recommended metal standoff height is

0.56 inch (14.3 mm) to provide adequate clearance. Note that the Methode

Socket (referenced in Table 6) in this case is not recommended, because its

minimum insertion depth requirement is not met. Use of metal 0.50 inch (12.7

mm) #6 standoffs together with metal spacers can achieve this. Alternately,

metal 0.56 inch (14.3 mm) #6 standoffs alone will be adequate. For the TP/XF

and TP/FT-10F control modules, 0.50 inch (12.7 mm) #6 metal standoffs alone are

recommended.
Figure 8 on page 12 presents the height restrictions of the component side of the

control module. The board is divided into two height zones: the maximum height

of components in the first zone is 0.20 inch (5.1 mm). The second zone's

components are 0.47 inch (11.93 mm) for the TP/XF and TP/FT-10F control

modules and 0.555 inch (14.1 mm) for the TP/FT-10 control module. Care should

be taken to ensure that no components on the application electronics board

interfere with the height restricted areas of the control modules.
Figure 9 on page 13 shows the recommended PCB pad layout for the application

electronics board to interconnect a control module with an application board that

has socket strips mounted on the component side.