Wire characteristics, Cable terminations – free topology, Cable terminations – doubly terminated bus – Echelon LonWorks Twisted Pair Control Module User Manual
Page 29
LonWorks Twisted Pair Control Module User's Guide
21
Wire Characteristics
Due to the many cabling and termination options available for the TP/FT-10
channel, please refer to the Series 5000 Chip Data Book, FTT-10 Free Topology
Transceiver User's Guide, or FTT-10A Free Topology Transceiver User's Guide, as
applicable, for information on wire characteristics and terminations.
The Junction Box and Wiring Guidelines for Twisted Pair LonWorks Networks
engineering bulletin (005-0023-01) provides a list of cable vendors for each type of
supported cable. This bulletin is available from the Echelon Web site
Cable Terminations – Free Topology
In a TP/FT-10 free topology segment, only one termination is required and can be
placed anywhere on the free topology segment. There are two choices for the
termination:
1. RC network (see Figure 10), with R1 = 52.3 Ω.
2. LPI-10 or LPI-11 Link Power Interface, with jumper at "1 CPLR" setting.
Figure 10. RC Network Termination for TP/FT-10 Segments
Cable Terminations – Doubly Terminated Bus
In a TP/FT-10 doubly terminated bus topology, two terminations are required,
one at each end of the bus. There are two choices for each termination:
1. RC network (see Figure 10), with R1 = 105 Ω.
2. LPI-10 or LPI-11 Link Power Interface, with jumper at "2 CPLR" setting
if resident on a link power segment. Only one LPI-10 or LPI-11 Interface