Air-Cooled Condensers

— Periodically inspect and

clean depending on operating conditions. Refer to
Start-Up and Service Instructions pertaining to

air-cooled condenser used.

Sight Glasses

— Provided at inlet of each expansion

valve. Units may be field charged by using the sight
glass (see Charging Procedure).

Charging Procedure

UNITS 5 OB A (WATER-COOLED CONDENSER)
— Units are shipped with a full operating charge of
refrigerant. If recharging is necessary (complete

charge lost), weigh in amount of refrigerant as

indicated on unit nameplate and Table 1. If unit
has partial charge, unit may be charged with sight
glass using standard refrigerant charging tech­
niques. Adjust water regulating valve to proper
saturated condensing temperature (168 to 226
psig).

Refrigerant can be added to 50BA008 and 012

units after sight glass is cleared to take advantage

of subcooling feature of these condensers. Add
refrigerant as follows:

50BA008 - 2.5 lbs
50BA012 - 0.5 lbs

The condenser on the 50BA064 unit has a liquid
level test cock. Adding liquid refrigerant to level of

test cock wül provide 12 to 15 F of subcooling.

UNITS 50BB (REMOTE, AIR-COOLED CON­
DENSERS) ^ Units are shipped with holding

charge only. Open suction and discharge line
service valves. Blow holding charge, evacuate and
leak test system. Add sufficient refrigerant vapor
to permit continuous operation after starting unit.

Review Start-Up Instructions. Using standard

refrigerant charging techniques, add refrigerant
required to maintain operating conditions. See
charging chart information supplied with con­
denser. If information is not available, block off
enough of condenser coil to maintain a discharge
pressure of 220 psig and charge to a clear sight

glass.

#

For replacement items use Carrier Specified Parts.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Tab 18

Form 50BA-4SI Supersedes 50BA-3SI

Printed in U S A

8-77

PC 111

Catalog No 535-098

Book

1

4

Tab

2a

7b

#

This manual is related to the following products: