beautypg.com

Attempt, For a, The problem – Carrier 30H User Manual

Page 8: Been, Corrected

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

FOUR FUNCTION TIMER

Refer to Fig. 4 — Timer Cycle. The functions are

as follows:

Switch A (Contacts A-Al, A-A2) runs the timer

motor. This provides a minimum of 5-1/2 minutes
after the compressor stops before it can restart, to
prevent short cycling (Time Guard® control).

Switch B (Contacts B-Bl, B-B2) provides 1-second

time delay for part-winding start and also provides a
lock-out function.

Switch D (Contacts D-D 1) provides a 2-1 / 2 minute
bypass of the low-pressure switch at start-up to
prevent nuisance trips under cold-start conditions.

Switch

E

(Contacts

E-El)

provides

a

35-second

bypass of the oil safety switch (OPS) at compressor
start-up (when OPS is used). If sufficient oil pressure
does not build up in this time, the compressor stops.

POSITION DURING UNIT OPERATION,

0 OR 8 MIN,

!

!

DD2 1

------ 2-6

SEC 1

--------------------- 150

SEC^-^

----------------

— +

-55 MIN-

NOTE:

black

DENOTES CLOSED CONTACTS

Fig. 4 Timer Cycle

OIL PRESSURE SAFETY SWITCH (OPS)

This control is available as an accessory. Refer to

Fig. 5 for field wiring connections.

The pressure switch is factory set at the following

pressures and should not be adjusted in the field:

SWITCH POSITION

Close on rise
Open on fall

PRESSURE SETTING

9-12 psi diff
4- 6 psi diff

The oil pressure safety switch is wired in parallel

with Switch E of the 4-function timer. This arrange­
ment

allows

approximately

35

seconds

for

oil

pressure to reach normal operating level after com­
pressor start. If the oil safety switch does not close

within 35 seconds, the compressor shuts down.

To

restart

the

compressor,

the

control

circuit

ON-OFF switch must be pressed to OFF and then to
ON. The timer will start and after approximately
5.5 minutes the compressor will start. If normal oil
pressure is established within the next 35 seconds,
the compressor continues to run. If, however, the oil
pressure does not reach a safe level, the compressor
stops at the end of the 35 seconds and locks out.

CAUTION; Do not

attempt

to restart the com­

pressor

for a

second time until

the problem

has

been

determined and

corrected.

REMOVE ORANGE WIRE

OPS — Oil Pressure Safety Switch
TB — Terminal Board

Fig. 5 — Oil Pressure Safety Switch to Control

Box Wiring Connections

Check Unit Safety Devices

SAFETY THERMOSTAT (Fig. 6)

This low water temperature cutout (LWTC) pro­

tects the unit against freeze-up due to operating
malfunction. The sensing bulb is inserted into a well
located in the

leaving water nozzle. As installed, the

standard control is factory set to open at 36 ±2 F,
breaking the control circuit and locking out the unit.
The contacts remake at 5

+ 2 F above the cutout

point, but the control circuit switch must be pressed
to OFF and then to ON for unit restart. This action
reenergizes the control circuit and starts the timer
under Time Guard® control.

The thermostat is designed to cut out in a range

down to -30 F, but to obtain this range, the low-limit

stop tab on the underside of the dial must be either
cut or bent.

Make this adjustment only if necessary

(when cooling glycols or brines).

n u

LOW LIMIT STOP TAB

f

Fig. 6 — Safety Thermostat

(No. HH22CC050 Shown)