Fig. 9 — cylinder bank loaded – Carrier 30H User Manual
Page 10
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
![background image](/manuals/717707/10/background.png)
Example;
Design setpoint is at 44 F. On a reduction in load,
the capacity of the unit will be reduced to zero
when return water temperature drops to 44 F, and
unit will cycle off.
WARNING:
Any
alteration
of factory settings,
except design setpoint, without Carrier authori
zation, may void the Carrier
warranty.
DESIGN SETPOINT ADJUSTMENT
When unit is ready for operation, insert small
screwdriver in adjusting slot (Fig. 8) and rotate to
turn dial (dial may also be turned by hand). Rotate
until the design setpoint for the installation appears
directly under the pointer. Insert a thermometer in
the
return chilled water connection and allow the
unit to run thru a cycle. At the instant the last step of
capacity unloads (switch no. J opens), read the tem
perature. If it is not the same as the dial reading, the
variation can be compensated by shifting the control
point slightly.
('.•\l ' I K ; N : Do not force the dial past the stop.
This could cause loss of the control point and
damage
the instrument.
/ ■. '
ADauSTtNS
SLOT.
LEAVING
WATER
TEMP(F)
DESIGN
POINTER
STOP
CALIBRATED «AL
Fig. 8 — Setpoint Adjustment
CYLINDER UNLOADING SYSTEM
Each unloading device is of the cylinder head
bypass type and unloads 2 cylinders when operating
solenoid is energized. Cylinder unloaders are ener
gized
and
de-energized
by
load
switches
in
the
temperature controller.
Steps under Cylinder Bank Loaded and Cylinder
Bank
Unloaded
refer
to
numbered
callouts
on
Fig. 9 and 10.
Cylinder Bank Loaded (Fig. 9)
1.
With solenoid valve
not energized, gas bypass
port is closed by solenoid valve stem.
2.
Discharge manifold pressure extends thru the
strainer
and
bleed
orifice
into
solenoid
valve
stem chamber and behind bypass piston.
3.
Refrigerant
pressure
overcomes
bypass
valve
spring pressure and forces piston forward closing
the bypass from the discharge manifold to the
suction manifold.
4.
Cylinder bank discharge pressure forces open the
discharge
piston
check
valve.
Refrigerant
gas
enters the discharge manifold.
As long as the solenoid valve is
not energized, the
cylinder bank will continue to operate fully loaded.
,, i
Fig. 9 — Cylinder Bank Loaded
Cylinder Bank Unloaded (Fig. 10)
1. When solenoid valve is energized, gas bypass port
is opened by solenoid valve stem.
2.
Discharge manifold pressure extends into sole
noid
valve
stem
chamber
and
behind
bypass
piston.
3.
Open gas bypass port allows pressure to bleed
into suction manifold causing reduction of pres
sure behind bypass piston.
4.
When bypass valve spring pressure overcomes
gas
pressure
behind
piston,
the
piston
moves
back, opening bypass from discharge manifold to
suction manifold.
5.
Cylinder discharge pressure on face of check
valve piston is reduced and discharge manifold
pressure closes check valve. The cylinder bank is
now isolated from discharge manifold.
As long as solenoid valve is energized, cylinder
bank will operate fully unloaded.
D
ischarge
FlSTON
CHECK VALVE
ASSEMBLY
DISCHARGE
MANIFOLD
f
Fig. 10 — Cylinder Bank Unloaded
1 0