TROUBLESHOOTING GUIDE (Coni)

SYMPTOM
System noises

Chattering unloader

Freeze-up

Hot liquid line

Frosted liquid line

Compressor will not unload

Compressor will not load

PROBABLE CAUSE

Piping vibration

Expansion valve hissing

Compressor noisy

REMEDY
Support piping as required.
Check for loose pipe connectors.

Add refrigerant.

Check for plugged liquid line
strainer.

Check valve plates for valve noise.
Replace compressor (worn
bearings).

Stuck check valve in valve plate

Improper charging

■ Improperly set safety thermostat

Operating with safety thermostat

bypassed

Improper circulation of chilled

water

System not drained for winter
shutdown

High suction

: Shortage of refrigerant due to leak

: Expansion valve opens too wide

Receiver shutoff valve partially

closed or restricted.

Restricted filter-drier

Burned out coil
Leaky bypass piston
Stuck needle valve

Miswired solenoid
plugged bypass port (low side)

Weak bypass piston spring

Damaged bypass piston
Stuck needle valve

i Miswired solenoid

Plugged bypass port strainer
(high side)

Stuck check valve in valve plate

Check for loose compressor hold­
down bolts.

Examine check valve components,
clean or replace as necessary.

Make sure that a full quantity of

water is flowing thru the cooler
while charging and that suction

pressure in cooler is equal to or
greater than that corresponding to

32 F (58 psig for Refrigerant 22).

Check safety thermostat for proper
setting at beginning of each
season.

if thermostat was bypassed for

checking, be sure it is back in the
circuit before starting the unit.

Use ample size cleanable strainer
in the chilled water circuit. Make
sure strainer is clean. It may some­
times be necessary to chemically
treat the water to prevent forma­
tion of deposits.

Be sure and remove drain plugs at
end of cooling season. Blow out
any residual water. Instead of
draining, a suitable antifreeze may
be added to the water. Damage to
the chiller due to freezing is con­
sidered abuse and is not covered

by the warranty.

Repair leak and recharge.

Adjust expansion valve.

Open valve or remove restriction.

Remove restriction or replace

filter-drier core.

Replace coil.
Clean or replace.
Clean.

Wire correctly.

Clean.

Replace.

Replace.
Clean.

Wire correctly.

Clean.

Examine check valve components,

clean or replace as necessary.

15