beautypg.com

Initial check, Start-up and service, Warning – Carrier 30H User Manual

Page 5: Power, Before proceeding with, Shut, Unit, Any service work. initial check

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

COMPLETE UNIT

Table 4 — Electrical Data; 3-Phase, 60-Hertz

Nameplate

VOLTS

200

230

460

575

06E COMPR

Supply Range"

180-229

207-264

414-528

518-660

USAGEt

Max

Max

Max

Max

UNIT 30

MKW

MCA

Fuse

MCA

Fuse

MCA

Fuse

MCA

Fuse

Cl rcuit

Amps

Amps

Amps

Amps

l' (

l

(^''' 2'{R) /^

040

50.4

194

250

167

225

84

110

68

90

B250 B250

H 050

61.1

230

300

207

300

104

150

84

125

I

J275 B250

060

71.8

259

350

239

300

120

150

97

125

J275 ; J275

INDIVIDUAL COMPRESSORS

COMPR

200 V

230 V

460 V

... 575........................

UNIT 30

nctr KW

06 E

RLA

LRA

; MTA

RLA LRA

MTA

RLA

LRA

MTA RLA

LRA MTA

; 040

250 (2) 25 2

86

345

; eo..;

74 300

102

37

150

50

30

120 42

275 (L) 35.9

11 5

506

' 80 "

106 440

"i 72.......... ''

53

220

73

43

176 58

П L/OU

250 (R) 25.2

86

345

74 300

;

102

37

150

50

30

;

120 42

060

275 (2) 35.9

115

506

Í" 80"

106 440

1......72 ' 1

53

220

73

43

176

:

58

6-Pole Breakers: values shown are for each 3-poie
section.

KW — Maximum Power Input (compressor)
LRA — Locked Rotor Amps
MCA — M inimum Circuit Amps. Complies with National Elec­

trical Code (NEC), Section 430-24.

MKW — Unit Power Input at operating conditions of 50 F Leaving

Chilled

Water

Temperature

(44

F

Saturated

Suction

Temperature)

and

145

F

Saturated

Discharge

Temperature.

MTA — Must Trip Amps (Factory-installed circuit breaker)
RLA — Rated Load Amps

*Untts are suitable for use on electrical systems where voltage

supplied to the unit terminals is not below or above the range
limits shown.

fPrefix: B, J = 1 electric unloader.

ELECTRICAL

BOX

CONTROL

SECTION

Inside this section are: relays, high- and low-

pressure

cut-outs,

low

water-temperature

cut-out,

timer,

terminal

strips

and

a

4-step

temperature

controller. On the outside (control panel) are: con­
trol

circuit

ON-OFE

switch,

partial

load

switch,

compressor

transfer

switch,

compressor

run

light,

safety trip lights and control circuit fuse. The control
panel is hinged to provide easy access to the controls
inside.

ELECTRICAL BOX, POWER SECTION

The main electrical power supply is brought in

thru the top of the electrical box, on the left-hand

side (see Fig. 1). The hole is suitable for accommo­
dating

3-in.

conduit.

Pressure-lug

connections

on

the terminal block are suitable for copper, copper-
clad aluminum or aluminum wire.

In this section are: main power terminal block,

compressor

circuit

breakers

with

calibrated

mag­

netic

trip

(for

compressor

motor

overload

and

locked rotor protection) and compressor motor con­
tactors. The panel over this section is secured with

screws as a safety measure against casual entry for
purposes other than service.

START-UP AND SERVICE

WARNING:

Shut

off

all

power

to

the

unit

before proceeding with

any service work.

INITIAL CHECK

Do not start the liquid chiller even momentarily

until the following steps have been completed.

1.

Check all auxiliary components such as chilled

liquid circulating pump, cooling tower if used,
air handling equipment, or other equipment to
which the chiller supplies liquid. Consult the
manufacturer’s instructions.

2.

Check

safety

thermostat.

See

Safety

Thermostat.

3.

Determine if there is a refrigerant charge in the

system. See Check Refrigerant Charge.

4.

Backseat (open) compressor suction and dis­

charge shutoff valves.

5. Open liquid line shutoff valves.

6.

Fill chilled liquid circuit completely with clean

water or other noncorrosive fluid to be cooled.

Bleed all air out of high points of system.

7. Fill cooling tower for condenser cooling water.

8. Set temperature controller.

9. Check tightness of all electrical connections..

10.

Check

compressor

oil

(should be

visible in

bull’s-eye). Refer to Check Oil Charge.

11.

Be sure crankcase of each compressor is warm

(heaters

should

be

on

for

24

hours

before

starting compressors).

12.

Be sure compressors are floating freely. See

INSTALLATION, Step 3.