TROUBLESHOOTING GUIDE

SYMPTOMS
Compressor does not run

Compressor cycles on low-
pressure control

Compressor loses oil

Frosted or sweating suction fine

Compressor cycles on low-
pressure control
Compressor cycles on high-

pressure control

Unit operates long or

continuously.

PROBABLE CAUSE
Power line open

: Control circuit breaker tripped

Safety tripped

Tripped power breaker

Condenser circulating pump not
running

■ Loose terminal connection

Improperly wired controls

’ Low line voltage

Compressor motor defective

Seized compressor

Low-pressure control erratic in
action

Compressor suction valve leaking

I Compressor suction shutoff vaive

partially closed

Low refrigerant charge

Leak in system

Mechanical damage (blown piston
or broken discharge valve)

Oil trapped in line

Crankcase heaters not energized

: during shutdown

Expansion vaive admitting excess
refrigerant

Plugged compressor suction

strainer

High-pressure

control

erratic

in action

Compressor discharge valve
partially closed.

Air in system

Condenser scaled

Condenser water pump orfans not
operating

Low refrigerant charge

Control contacts fused

Air in system

Partially plugged or plugged

expansion valve or strainer

Defective insulation

Service load too high

Inefficient compressor

REMEDY ........... ............. ..................
Check fused disconnect. Replace

fuse if blown^

Check control circuit for ground or
short.

Reset breaker.

Reset.
Check the controls. Find cause of

trip and reset breaker.

Power off — restart.

Pump binding — free pump.

Incorrect wiring — rewire.

Pump motor burned out — replace.

Check connections.

Check wiring and rewire.

Check line voltage — determine
location of voltage drop and
remedy deficiency.

Check motor winding for open or
short. Replace compressor, if
necessary.

Replace compressor.

Raise differential setting.

Check capillary for pinches.

Replace control if defective.

Replace valve plate.

Open valve.

Add refrigerant.

Repair leak.

Repair damage or replace
compressor.

Check piping for oil traps.

Check wiring and crankcase

heater relay. Replace heater if
necessary.

Adjust expansion vaive. Replace
valve if defective.

Clean strainer or replace.

Check capillary tube for pinches.

Set control as required.

Open valve, or replace if defective.

Purge.

Clean condenser.

Start pump — repair or replace if
defective.

Add refrigerant.

Replace control.

Purge.

Clean or replace.

Repair or replace.

Keep doors and windows closed.

Check valves, replace if necessary.

14