Check refrigerant charge, Start-up and operation checks – Carrier 30H User Manual
Page 6
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Check Refrigerant Charge
1MP(.)R'1 \N T; Do not t>pi;n liquid \al\t' or
«-•omprcssor ciisdniiiie \al\o uinil it is deter
mined
that there is a charge in the remainder of
the system. .1
¡h‘.sin\i- /ircs'.urc u;// induuh' a
iharj^f m ¡hi'
s i v / i v / /
The
units
are
shipped
with
a
full
refrigerant
charge (see Table 2). However, if it is necessary to
add refrigerant, the unit should be operated for
some time at full capacity and then charge can be
added until the sight glass is clear of bubbles. For
maximum liquid subcooling, the liquid level should
be up to the liquid level test cock located on the
shell, near the end, of each tower condenser. This
usually
requires
additional
refrigerant
charge
beyond the amount to clear the sight glass (see
LIQUID CHARGING METHOD).
If there is no refrigerant vapor pressure in the
system, the entire system must be leak tested. After
repair of leaks, the system must be evacuated before
recharging.
See
Standard
Service
Techniques
Manual, Chapter 1, Refrigerants, for leak testing,
evacuation and charging procedures.
C.M.' nON; When adjusting rdrigerant charge.
Circulate
water thru the condenser and cooler at
ail times to prevent frec/ing. Frec/ing damage is
considered abuse and is not covered by Carrier
warrants.
The liquid charging method is recommended for
complete
charging
or
when
additional
charge
is
required.
LIQUID CHARGING METHOD
C.\U i'lON; Be careful not to overcharge s\s-
tem. Oserchaigmg results in higher discharge
pressure with higher cooling water consurnp-
tion, possible compressor damage, higher power
consumption.
Charge thru I / 4-in. flare connection on liquid line
shutoff valve.
Never charge liquid into the low-
pressure side of the system.
1. Frontseat (close) liquid line shutoff valve.
2.
Connect a refrigerant cylinder loosely to charg
ing
valve
connection.
Purge
charging
line
and
tighten connections.
3. Open liquid line shutoff valve.
4.
If system has been dehydrated and is under
vacuum,
break
vacuum
with
refrigerant
(gas
charge). Build up system pressure to 58 psi for
R-22 (32 F). Invert refrigerant cylinder so that
liquid refrigerant will be charged.
5. a. For complete charge, see “Charging” in
Standard
Service
Techniques
Manual,
Chap
ter
1,
Refrigerants.
Follow
Charging
By
Weight
procedure.
(When
charge
is
nearly
full, complete process by observing sight glass
for clear liquid flow.)
b.
For
complete
charge
where
refrigerant
cylinder
cannot
be
weighed,
or
for
adding
refrigerant,
follow
the
procedure
Charging
By Sight Glass in the manual.
6.
To
ensure
maximum
subcooler
performance,
check liquid level in tower condensers by means
of test cock located on each condenser shell near
right end tube sheet. Liquid discharge from test
cock indicates fully charged subcooler.
Check Oil Charge
— All units are factory charged
with oil. If oil is visible in sight glass, check the unit
for operating readiness as described in the section,
Initial Check; then start compressor. Observe level
and add oil, if required, to bring level in erankcase
! / 8 to 3/ 8^ of bull’s-eye during steady operation. To
add or remove oil, see Standard Service Techniques
Manual, Chapter 1, Refrigerants.
Use only Carrier approved compressor oil. Do
not reuse drained oil or use any oil that has been
exposed to atmosphere.
Approved compressor oils:
Sun Oil Co.
Suniso 3GS
Texaco, Inc.
Capella BI
E.I. DuPont Co.
DuPont Synthetic Refrig
eration Oil, 150 SSU only
TO ADD OIL
Close
suction
shutoff
valve
and
pump
down
crankcase to 2 psig (low-pressure cutout must be
bypassed with a jumper). Wait a few minutes and
repeat as needed until pressure remains at 2 psig.
Close diseharge shutoff valve. Remove oil fill plug
above bull’s-eye, add oil thru plug hole and replace
plug.
Reopen
suction
and
discharge
valves.
Run
compressor for about 20 minutes and check the oil
level.
TO REMOVE OIL
Pump down eompressor to 2 psig. Close suetion
and discharge valves. Loosen the 1/4-in. pipe plug
in compressor base and allow the oil to seep out
past the threads of the plug.
The crankcase will be
under slight pressure. Be careful not to remove the
plug; the entire oil charge may be lost. Small
amounts of oil can be removed thru oil pump dis
charge connection while compressor is running.
START-UP AND OPERATION CHECKS
Start-up should be performed only under super
vision
of
experienced
refrigeration
mechanic.
Be
sure crankcase heaters have been energized for 24
hours.
1.
Open all system valves that may have been
closed during or after charging.
2.
Check
air-handling
equipment,
chilled
water
and
condenser
water
pumps,
and
any
other
equipment eonneeted to chiller.
3. Start unit by firmly pushing ON button.
4. Check all controls for proper operation.