beautypg.com

Check refrigerant charge, Start-up and operation checks – Carrier 30H User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Check Refrigerant Charge

1MP(.)R'1 \N T; Do not t>pi;n liquid \al\t' or

«-•omprcssor ciisdniiiie \al\o uinil it is deter­

mined

that there is a charge in the remainder of

the system. .1

¡h‘.sin\i- /ircs'.urc u;// induuh' a

iharj^f m ¡hi'

s i v / i v / /

The

units

are

shipped

with

a

full

refrigerant

charge (see Table 2). However, if it is necessary to
add refrigerant, the unit should be operated for
some time at full capacity and then charge can be

added until the sight glass is clear of bubbles. For
maximum liquid subcooling, the liquid level should
be up to the liquid level test cock located on the
shell, near the end, of each tower condenser. This
usually

requires

additional

refrigerant

charge

beyond the amount to clear the sight glass (see

LIQUID CHARGING METHOD).

If there is no refrigerant vapor pressure in the

system, the entire system must be leak tested. After
repair of leaks, the system must be evacuated before
recharging.

See

Standard

Service

Techniques

Manual, Chapter 1, Refrigerants, for leak testing,

evacuation and charging procedures.

C.M.' nON; When adjusting rdrigerant charge.

Circulate

water thru the condenser and cooler at

ail times to prevent frec/ing. Frec/ing damage is
considered abuse and is not covered by Carrier

warrants.

The liquid charging method is recommended for

complete

charging

or

when

additional

charge

is

required.

LIQUID CHARGING METHOD

C.\U i'lON; Be careful not to overcharge s\s-
tem. Oserchaigmg results in higher discharge

pressure with higher cooling water consurnp-

tion, possible compressor damage, higher power

consumption.

Charge thru I / 4-in. flare connection on liquid line

shutoff valve.

Never charge liquid into the low-

pressure side of the system.

1. Frontseat (close) liquid line shutoff valve.

2.

Connect a refrigerant cylinder loosely to charg­

ing

valve

connection.

Purge

charging

line

and

tighten connections.

3. Open liquid line shutoff valve.

4.

If system has been dehydrated and is under

vacuum,

break

vacuum

with

refrigerant

(gas

charge). Build up system pressure to 58 psi for

R-22 (32 F). Invert refrigerant cylinder so that

liquid refrigerant will be charged.

5. a. For complete charge, see “Charging” in

Standard

Service

Techniques

Manual,

Chap­

ter

1,

Refrigerants.

Follow

Charging

By

Weight

procedure.

(When

charge

is

nearly

full, complete process by observing sight glass
for clear liquid flow.)

b.

For

complete

charge

where

refrigerant

cylinder

cannot

be

weighed,

or

for

adding

refrigerant,

follow

the

procedure

Charging

By Sight Glass in the manual.

6.

To

ensure

maximum

subcooler

performance,

check liquid level in tower condensers by means

of test cock located on each condenser shell near
right end tube sheet. Liquid discharge from test
cock indicates fully charged subcooler.

Check Oil Charge

— All units are factory charged

with oil. If oil is visible in sight glass, check the unit
for operating readiness as described in the section,

Initial Check; then start compressor. Observe level
and add oil, if required, to bring level in erankcase

! / 8 to 3/ 8^ of bull’s-eye during steady operation. To

add or remove oil, see Standard Service Techniques

Manual, Chapter 1, Refrigerants.

Use only Carrier approved compressor oil. Do

not reuse drained oil or use any oil that has been
exposed to atmosphere.

Approved compressor oils:

Sun Oil Co.

Suniso 3GS

Texaco, Inc.

Capella BI

E.I. DuPont Co.

DuPont Synthetic Refrig­

eration Oil, 150 SSU only

TO ADD OIL

Close

suction

shutoff

valve

and

pump

down

crankcase to 2 psig (low-pressure cutout must be
bypassed with a jumper). Wait a few minutes and

repeat as needed until pressure remains at 2 psig.
Close diseharge shutoff valve. Remove oil fill plug
above bull’s-eye, add oil thru plug hole and replace
plug.

Reopen

suction

and

discharge

valves.

Run

compressor for about 20 minutes and check the oil
level.

TO REMOVE OIL

Pump down eompressor to 2 psig. Close suetion

and discharge valves. Loosen the 1/4-in. pipe plug
in compressor base and allow the oil to seep out
past the threads of the plug.

The crankcase will be

under slight pressure. Be careful not to remove the

plug; the entire oil charge may be lost. Small

amounts of oil can be removed thru oil pump dis­
charge connection while compressor is running.

START-UP AND OPERATION CHECKS

Start-up should be performed only under super­

vision

of

experienced

refrigeration

mechanic.

Be

sure crankcase heaters have been energized for 24
hours.

1.

Open all system valves that may have been

closed during or after charging.

2.

Check

air-handling

equipment,

chilled

water

and

condenser

water

pumps,

and

any

other

equipment eonneeted to chiller.

3. Start unit by firmly pushing ON button.

4. Check all controls for proper operation.