26H
S E R V I C E
Carrier
OBSERVATION
POSSIBLE CAUSE
REMEDY AND REFERENCE
SECTIONS
Plugged capillary, either
due to moisture, dirt or
crimped capillary
Purge charge; install new strainer-
drier. If capillary is damaged, re
place accumulator assembly
(includes capillaries )
3, 7 & 8
Cubes "hanging-up" on
ice deflector screen
Reposition deflector screen
Installation
17
Examine evaporator for warped
or bulged freezing columns
10
Bln thermostat "cut
out " setting may be too
high
Adjust and check
30
Installation
2
Poor water distribution
due to scale on spreader
plates and/or clogged
screen on water pump
Recenter spreader plates and
water header nozzles
Clean water circuit, including
water pan and water pump screen
10, 12 & 15
15
Low refrigerant charge
Check charge and time of
freezing cycle
4
17. Irregular shaped
cubes, or mixture of
good and shell cubes.
Evaporator tubing pulled
loose from freezing columns
Replace evaporator
10
Cubes restricting one or
more columns
Examine deflector screen and ice
columns, remove obstructions
Installation
15
Raise main control "cut-in"set
ting slightly (this will increase
defrost time)
28
Float valve set too high.
Standpipe not seated
Reset float valve; check for leaky
fl(5at valve. Seat standpipe pro
perly.
Installation
16
Bin thermostat pre
maturely cuts off unit
Check for a faulty bin therm
ostat; check settings
30
Temporary power failure
during "freezing cycle"
Turn unit "off "permit ice to melt
out of columns; start unit when
power is restored
Cubes hanging up in
columns due to bulged
tubes
Check freezing columns. Replace
evaporator if columns are bulged
10
26H-57PD