Carrier
S E R V I C E
26H
«
OBSERVATION
POSSIBLE CAUSE
REMEDY AND REFERENCE
SECTIONS
12. Continuous running and
Faulty main control, or
Replace if necessary
28
freezing
well capillary scaled
Check main control capillary
position in well
28
Replace if ice does not actuate
control from freezing cycle to
defrost cycle when held against
main control capillary (cut-out)
side
28
Overflow water not reach-
Scale and foreign particles may plug
15 & 28
ing overflow well and main
overflow trough tube. Check posi-
control bulb
tion of control bulb. Also check
leveling of machine
13. Unit fails to return to
Main control "cut-in " bulb
Replace main control
28
freeze cycle
has lost its charge
Low ambient temperature
Unit will not operate at ambient
Installation
temperatures below 50°
2
14. Unit continues to run
Bin control contacts fused
Replace control
30
with full bunker.
Cutout setting too low
Adjust and check
30
Ice not reaching bin
control bulb
15. Water overflowing from
Loose electrical connections
machine section
Main control, safety overflow
Check wiring and possibility of
28-29 & 30
switch or bin control failed to
stop freezing cycle
faulty controls
Leak in water pump circuit
Check water hoses and header
11 & 12
UNSATISFACTORY CUBES
16. Thin wall cubes
Manually shutting unit off
Normal as a result of such a
18
"shells ".
during a freezing cycle
shut-down. Instruct owner to
wait until end of defrost cycle
before shutting off unit
Short defrost cycle (cubes
Check main control setting; may
28
remaining in freezing
require raising cut in point
columns)
Check refrigerant charge
4
Check safety switch
27
57
26H-57PD