Charging with refrigerant, Carrier – Carrier 26H User Manual
Page 26
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
26H
S E R V I C E
Carrier
4. CHARGING WITH REFRIGERANT
TABLE 1 - REFRIGERANT CHARGE (R12)
MODEL
IDENTIFICATION
CHARGE
26H5
No changes
3 lb. 8 oz.
26H3
9 " condenser and 9 " accum.
1 lb. 11 oz.
26H3
Serial No. 331784 Change to 18"cond.-
2 lb. 3 oz.
9 " accumulator
26H3
Serial No. 411152 change to 15"cond.-
2 lb. 3 oz.
9 " accumulator
26H3
Serial No. 510446 change to 15"cond.—
10 1/2" accumulator
2 lb. 9 oz.
If the unit is undercharged, back seat the suction
shutoff valve. Remove a gauge port plug from the
valve; connect a charging line from a drum of re
frigerant 12. Tighten this line at the drum, but make
a loose connection at the suction shutoff valve.
Crack the valve on the drum so that refrigerant va
por will force air from the charging line out the
loose connection. After purging the air from the
charging line, tighten the connection at the suc
tion shut-off valve. Open the suction valve to a
point midway between the back-seated and front-
seated positions. With the suction shutoff valve in
this position, it is possible to read the system pres
sure during the charging period. The refrigerant 12
drum should be in an upright position to admit va
por only.
If the unit is overcharged, turn the unit off. Back
seat the discharge shutoff valve. Attach a charg
ing line to one of the gauge ports in the valve and
attach a charging manifold to the other end of the
charging line. Turn the shutoff valve to the middle
position; start the unit. Bleed refrigerant from the
charging manifold in 5-second intervals until the
charge is correct. Turn the unit off. Back seat the
shutoff valve and remove the charging line. Replace
the gauge port plug and start the unit.
WEIGHING IN CHARGE
The most accurate method of charging a refrigerant
system is weighing in the charge. Proceed as fol
lows:
1. Bleed any charge remaining in the system,
then start the compressor and pump out the
system through the discharge valve.
2. With the compressor still running, connect the
drum of refrigerant to the suction valve.
3. Back seat the discharge valve and immediately
turn off the compressor.
4. Weigh the drum of refrigerant (it is easier to
weigh a charge if the weight of the drum can
*, be checked during the charging process).
5. Open the suction valve and crack the valve
on the drum of refrigerant. Start the compressor.
6. Continue to charge until the scale shows the
proper amount of refrigerant has been fed into
the system.
7. Close the valve on the drum and then the suc
tion shutoff valve.
8. Disconnect the charging line.
9. Leak test the system.
i
t
26H-57PD
26