Table 2 — Electrical Data
UNIT
48 SERIES
VOLTS-PH-HZ
VOLTAGE
RANGE
COMPR
OUTDOOR
FAN MTR
INDOOR
FAN MTR
COMBUSTION
FAN MTR
POWER SUPPLY
Min
Max
RLA
LRA
Qty
FLA
Hp
FLA
FLA
MCA
MOCP (Amps)*
208/230-1-60
197
254
22 2
100
1
2 2
33
75
3 6
69
90
40
50
LDT004
208/230-3-60
187
254
15 1
100
1
22
33'^
75
3 6
6 9
90
30/30
45/45
460-3-60
414
508
7 6
36 5
1
1 1
"33
.75
3.5
57
15
25
208/230-1-60
197
254
28 1
106
1
29
75
6 9
.90
46
60
HDT/LDT005
208/230-3-60
187
254
18 3
105
1
29
75
6 9
.90
35
45/45
460-3-60
414
508
9 2
35
1
1.5
.75
3 5
.57
20
25
575-3-60
517
633
8 3
41
1
2 9
75
6 9
90
19
20
230-1-60
207
254
28 5
130
1
29
75
1 00
69
80
90
55
50
HDT/LDT006
208/230-3-60
187
254
20 9
98
1
2 9
75
1 00
69
80
90
40/40
45/45
LH006
460-3-60
414
508
104
49
1
1 5
75
1 00
3 5
40
57
20
25
575-3-60
517
633
8 3
41
1
29
75
1 00
80
69
90
30
45
230-1-60
207
254
28 5
130
1
29
50
75
69
80
90
55
50
HH006
208/230-3-60
187
254
20 9
98
1
29
50
75
69
80
90
40/40
45/45
460-3-60
414
508
104
49
1
1 5
50
75
3 5
40
57
20
25
575-3-60
508
623
8 3
41
1
29
50
75
69
80
90
30
45
HD/HH
007
208/230-3-60
187
254
26 7
137
1
29
75
1 00
3 6
48
90
40
42
60
460-3-60
414
508
12 1
69
1
1 5
75
1 00
1 8
2 4
57
18 5
19 5
30
575-3-60
518
632
9 6
51
1
2 9
1 00
7 5
90
22 4
30
HD.LD/
208/230-3-60
187
254
32 5
183
1
2 9
1 0
1 5
5 4
6 0
90
50/50
60/60
460-3-60
414
508
15 2
91 1
1
1 5
1 0
1 5
2 7
3 0
57
25
35
HH.LH
008
575-3-60
518
632
15 8
73 3
1
1 5
1 0
1.5
1 4
2 1
57
25
26
35
40
HDD.LDD/
HHD.LHD
008
208/230-3-60
187
254
15 2
(ea)
80
(ea)
1
29
1 0
1 5
48
6 5
90
43
45
50
50
460-3-60
414
508
7 2
(ea)
35
(ea)
1
1 5
1 0
1 5
24
33
57
21
22
25
25
#
FLA — Full Load Amps
LRA — Locked Rotor Amps
MCA -- Min imum Circuit Amps (for wire sizing) Complies with
NEC, Section 430-24
NOTES
1
In compliance with NEC requirements for multimotor
and
combination load equipment (ref NEC Articles 430 and 440),
the overcurrent protective device for the unit shall be fuse only
2 Unbalanced 3-Phase Supply Voltage
Never
operate
a
motor
where
a
phase
unbalance
in
supply
volt
age
IS
greater
than
2%
Use the following formula to determine
the % voltage unbalance
% Voltage Unbalance
max voltage deviation from average voltage
average voltage
Supply voltage is 460-3-60
AB = 452 volts
BC = 464 volts
AC = 455 volts
= 100
X -
Average Voltage
452
+
464 + 455
1371
3
457
MOCP — Maximum Overcurrent Protection
RLA — Rated Load Amps
'Fuse only
Determine maximum deviation from average voltage
(AB) 457 - 452 = 5 volts
(BC) 464 - 457 = 7 volts
(AC) 457 - 455 = 2 volts
Maximum deviation is 7 volts
Determine % voltage unbalance
% Voltage Unbalance = 100 x = 1 53%
457
This amount of phase unbalance is satisfactory as it is below
the maximum allowable 2%