Table 2 — Electrical Data

UNIT

48 SERIES

VOLTS-PH-HZ

VOLTAGE

RANGE

COMPR

OUTDOOR

FAN MTR

INDOOR

FAN MTR

COMBUSTION

FAN MTR

POWER SUPPLY

Min

Max

RLA

LRA

Qty

FLA

Hp

FLA

FLA

MCA

MOCP (Amps)*

208/230-1-60

197

254

22 2

100

1

2 2

33
75

3 6
69

90

40

50

LDT004

208/230-3-60

187

254

15 1

100

1

22

33'^
75

3 6
6 9

90

30/30

45/45

460-3-60

414

508

7 6

36 5

1

1 1

"33

.75

3.5

57

15

25

208/230-1-60

197

254

28 1

106

1

29

75

6 9

.90

46

60

HDT/LDT005

208/230-3-60

187

254

18 3

105

1

29

75

6 9

.90

35

45/45

460-3-60

414

508

9 2

35

1

1.5

.75

3 5

.57

20

25

575-3-60

517

633

8 3

41

1

2 9

75

6 9

90

19

20

230-1-60

207

254

28 5

130

1

29

75

1 00

69
80

90

55

50

HDT/LDT006

208/230-3-60

187

254

20 9

98

1

2 9

75

1 00

69
80

90

40/40

45/45

LH006

460-3-60

414

508

104

49

1

1 5

75

1 00

3 5
40

57

20

25

575-3-60

517

633

8 3

41

1

29

75

1 00

80
69

90

30

45

230-1-60

207

254

28 5

130

1

29

50

75

69
80

90

55

50

HH006

208/230-3-60

187

254

20 9

98

1

29

50
75

69
80

90

40/40

45/45

460-3-60

414

508

104

49

1

1 5

50
75

3 5
40

57

20

25

575-3-60

508

623

8 3

41

1

29

50
75

69
80

90

30

45

HD/HH

007

208/230-3-60

187

254

26 7

137

1

29

75

1 00

3 6
48

90

40
42

60

460-3-60

414

508

12 1

69

1

1 5

75

1 00

1 8

2 4

57

18 5
19 5

30

575-3-60

518

632

9 6

51

1

2 9

1 00

7 5

90

22 4

30

HD.LD/

208/230-3-60

187

254

32 5

183

1

2 9

1 0
1 5

5 4
6 0

90

50/50

60/60

460-3-60

414

508

15 2

91 1

1

1 5

1 0
1 5

2 7
3 0

57

25

35

HH.LH

008

575-3-60

518

632

15 8

73 3

1

1 5

1 0
1.5

1 4
2 1

57

25
26

35
40

HDD.LDD/

HHD.LHD

008

208/230-3-60

187

254

15 2
(ea)

80

(ea)

1

29

1 0
1 5

48
6 5

90

43
45

50
50

460-3-60

414

508

7 2

(ea)

35

(ea)

1

1 5

1 0
1 5

24
33

57

21
22

25
25

#

FLA — Full Load Amps
LRA — Locked Rotor Amps
MCA -- Min imum Circuit Amps (for wire sizing) Complies with

NEC, Section 430-24

NOTES

1

In compliance with NEC requirements for multimotor

and

combination load equipment (ref NEC Articles 430 and 440),
the overcurrent protective device for the unit shall be fuse only

2 Unbalanced 3-Phase Supply Voltage

Never

operate

a

motor

where

a

phase

unbalance

in

supply

volt­

age

IS

greater

than

2%

Use the following formula to determine

the % voltage unbalance

% Voltage Unbalance

max voltage deviation from average voltage

average voltage

Supply voltage is 460-3-60

AB = 452 volts

BC = 464 volts

AC = 455 volts

= 100

X -

Average Voltage

452

+

464 + 455

1371

3

457

MOCP — Maximum Overcurrent Protection
RLA — Rated Load Amps

'Fuse only

Determine maximum deviation from average voltage

(AB) 457 - 452 = 5 volts
(BC) 464 - 457 = 7 volts
(AC) 457 - 455 = 2 volts

Maximum deviation is 7 volts
Determine % voltage unbalance

% Voltage Unbalance = 100 x = 1 53%

457

This amount of phase unbalance is satisfactory as it is below
the maximum allowable 2%