beautypg.com

Carrier 48HDT User Manual

Page 13

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

supplied with accessory, on OAT. and set for 3 F
below indoor room thermostat setting.

If accessory enthalpy control is used in lieu of
OAT., refer to instructions shipped with
accessory.

9. Place outdoor air inlet screen in hood and

secure with retaining bracket across hood front.
See Fig. 16.

10. Replace upper filter access panel with screws

saved from step 1.

#

#

POWER FAILURE — Dampers have a spring
return. In event of power failure, dampers close
until power is restored. Do not manually operate

damper motor.

48HD,LD/ HDD,LDD008 — Optional economizer
is shipped with hood broken down in unit filter
section. See Fig. 21.

SPEED CLIPS

COOLING

LOCKOUT

SWITCH

(CLS)

OUTDOOR AIR THERMOSTAT

OR ENTHALPY CONTROL

OUTDOOR AIR HOOD SIDE PLATE

Fig. 20 — Enthalpy Control Position

(004,005,006,007 Units)

Fig. 21 — Access Panel Location

(008 Units)

Fig. 22 — Outdoor Air Hood Details

(008 Units)

BAROMETRIC

RELIEF

DAMPER LOCATION

BASE UNIT
RECEPTACLE

OUTDOOR AIR
INLET SCREENS (2)

CLS — Cooling Lockout Switch
EC — Enthalpy Control
OAT — Outdoor Air Thermostat

Fig. 23 — Economizer Installed in Unit

(008 Units)

Assembly

1. Remove protective cover from unit. See Fig. 21.

2. Remove upper filter access panel (save screws).

See Fig. 21.

3. Remove hood parts from unit evaporator fan

and filter area. Assemble hood top and side
plates as shown in Fig. 22. Remove tape from
barometric relief damper (see Fig. 23).

D o n ot

attach h ood to u n it at th is tim e.

Put aside

baffle, screen retainer and retainer screw for
later assembly.

13