Viconics VZ7260(X) VZ7656(X) BACnet Installation Manual User Manual
Page 9

9
Object Name
V
Z
76
56
R1
00
0
B
V
Z
76
56
H1
00
0
B
V
Z
76
56
F
10
00
B
V
Z
76
56
E
10
00
B
O
b
jec
t P
ro
p
er
ty
O
b
jec
t Typ
e
Inst
ance
#
Cfg Heating Lockout Temp
X
X
X
X
R/W
AV
2
Cfg High Balance Point
X
R/W
AV
24
Cfg Low Balance Point
X
R/W
AV
25
Cfg Maximum CO2 Level
X
R/W
AV
38
Cfg Maximum Fresh Air
X
R/W
AV
36
Cfg Minimum CO2 Level
X
R/W
AV
37
Cfg Minimum Fresh Air
X
R/W
AV
35
Cfg Minimum Supply Heat
Setpoint
X
R/W
AV
26
Cfg Mixed Air Setpoint
X
R/W
AV
31
Cfg Password
X
X
X
X
R/W
AV
23
Cfg Power-up Delay
X
X
X
X
R/W
AV
20
Cfg Return Air Occ CL Spt
X
X
X
X
R/W
AV
7
Cfg Return Air Occ HT Spt
X
X
X
X
R/W
AV
9
Cfg Return Air Unocc CL
Spt
X
X
X
X
R/W
AV
8
Cfg Return Air Unocc HT
Spt
X
X
X
X
R/W
AV
10
Cfg Static Pressure Spt
X
X
X
X
R/W
AV
4
Cfg Supply Heat Lockout
Temperature
X
R/W
AV
27
GUI Outdoor Temperature
X
X
X
X
R/W
AV
19
GUI AUX Status
X
X
X
R
BI
7
GUI BI Status
X
X
X
R
BI
6
GUI G Fan
X
X
X
X
R
BI
1
GUI W1 Heat
X
X
X
R
BI
4
GUI W2 Heat
X
X
R
BI
5
GUI Y1 Compressor
X
R
BI
16
GUI Y1 Cool
X
X
X
R
BI
2
GUI Y2 Compressor
X
R
BI
15
GUI Y2 Cool
X
X
X
R
BI
3
Sta Clock Alarm
X
X
X
X
R
BI
12
Sta Cooling Lockout Status
X
X
X
X
R
BI
9
Sta Discharge Temp Alarm
X
X
X
X
R
BI
13
Sta Filter Alarm
X
X
X
X
R
BI
11
Sta Fresh Air Alarm
X
R
BI
17