beautypg.com

Viconics VZ7260(X) VZ7656(X) BACnet Installation Manual User Manual

Page 8

background image

8

Device Object List for VZ7656 Models


Object Name

V

Z

76
56
R1
00
0

B

V

Z

76
56
H1
00
0

B

V

Z

76
56
F

10
00
B

V

Z

76
56
E

10
00
B

O

b

jec
t P
ro

p

er
ty

O

b

jec
t Typ

e

Inst

ance

#

GUI Discharge Air Temp

X

X

X

X

R

AI

1

GUI Analog Heat Output

X

R

AI

5

GUI By-Pass Damper / VFD

X

X

X

X

R

AI

4

GUI Return Air Temp

X

X

X

X

R

AI

2

GUI Static Pressure

X

X

X

X

R

AI

3

Cfg RTC MAC

X

X

X

X

R

AV

1

Cfg Device Instance

X

X

X

X

R

AV

21

GUI Highest PI Cool Demand

X

X

X

X

R

AV

18

GUI Highest PI Heat Demand

X

X

X

X

R

AV

17

GUI CO2 Level

X

R

AV

40

GUI Current Zone PI Cool
Demand

X

X

X

X

R

AV

12

GUI Current Zone PI Heat
Demand

X

X

X

X

R

AV

11

GUI Economizer Output

X

R

AV

42

GUI Fresh Air Level

X

R

AV

39

GUI Highest CO2 Zone

X

R

AV

41

GUI Highest PI Cool Zone

X

X

X

X

R

AV

16

GUI Highest PI Heat Zone

X

X

X

X

R

AV

15

GUI Supply PI Heat Demand

X

R

AV

28

GUI Transferred PI Cool
Demand

X

X

X

X

R

AV

14

GUI Transferred PI Heat
Demand

X

X

X

X

R

AV

13

Cfg Changeover Setpoint

X

R/W

AV

30

Cfg Cooling Lockout Temp

X

X

X

X

R/W

AV

3

Cfg Deadband

X

X

X

X

R/W

AV

22

Cfg Discharge High Limit Spt

X

X

X

X

R/W

AV

5

Cfg Discharge Low Limit Spt

X

X

X

X

R/W

AV

6

Cfg Economizer Max Position

X

R/W

AV

33

Cfg Economizer Min Position

X

R/W

AV

32

Cfg Fresh Air Max Range

X

R/W

AV

34

This manual is related to the following products: