Cfg Supply Heat Lockout

AV 27

-15°F(-26°C)

120°F(49°C)

32°F(0°C)

GUI Supply PI Heat Demand

AV 28

0%

100%

N/A

Cfg Changeover Setpoint

AV 30

14°F(-26°C)

70°F(-26°C)

55°F(13°C)

Cfg Mixed Air Setpoint

AV 31

50°F(10°C)

90°F(32°C)

55°F(13°C)

Cfg Economizer Min Position

AV 32

0%

100%

0%

Cfg Economizer Max Position

AV 33

0%

100%

100%

Cfg Fresh Air Max Range

AV 34

0 CFM (0 l/s)

20000 CFM

(9440 l/s)

0 CFM (0 l/s)

Cfg Minimum Fresh Air

AV 35

0 CFM (0 l/s)

20000 CFM

(9440 l/s)

0 CFM (0 l/s)

Cfg Maximum Fresh Air

AV 36

0 CFM (0 l/s)

20000 CFM

(9440 l/s)

0 CFM (0 l/s)

Cfg Minimum CO2 Level

AV 37

0 PPM

2000 PPM

800 PPM

Cfg Maximum CO2 Level

AV 38

0 PPM

2000 PPM

1200 PPM

GUI Fresh Air Level

AV 39

0 CFM (0 l/s)

20000 CFM

(9440 l/s)

N/A

GUI CO2 Level

AV 40

0 PPM

2000 PPM

N/A

GUI Highest CO2 Zone

AV 41

1

127

N/A

GUI Economizer Output

AV 42

0%

100%

N/A

Note:

The GUI Current Zone PI Heat & Cool Demand objects represent the actual calculated average demand values from either the
highest, the demands of the actual highest 3 zones or the demands of the actual highest 5 zones as per selected by MV2
Control Type object.