15

VZ7260 List of Property Enumeration Sets for MV Objects

Object Name

Object

Type and

instance

BACnet Index

Text

Default value

Cfg Zone Baud

MV 1

1

9600 ( Bps )

Auto

2

19200 ( Bps )

3

38400 ( Bps )

4

76800 ( Bps )

5

Auto

Cfg Reheat
Configuration

MV 2

1

None

None

2

Analog Duct Heater
Only

3

On/Off Duct Heater
Only

4

On/Off Perimeter
Heater Only

5

Analog Duct Heater
with On/Off Perimeter
Heater

Cfg BI1
Configuration

MV 3

1

None

None

2

Motion NO

3

Motion NC

Cfg PI Heat Weight

MV 4

1

0 %

100 %

2

25 %

3

50 %

4

75 %

5

100 %

Cfg PI Cool Weight

MV 5

1

0 %

100 %

2

25 %

3

50 %

4

75 %

5

100 %

Cfg Temporary
Occupancy Time

MV 6

1

0 hour

2 hours

2

1 hour

3

2 hours

4

3 hours

5

4 hours

6

5 hours

7

6 hours

8

7 hours

9

8 hours

10

9 hours

11

10 hours

12

11 hours

13

12 hours