VZ7656 Device Object Table


Object Name

Type and

Instance

Object Property

Controller Parameter

VZ7656

Device

Object_Identifier

Property 75 (R,W)

Unique ID number of a device on a network

Object_Name

Property 77 (R,W)

Unique name of a Device on a network

Model Name

Property 70 (R)

Controller Model number

Firmware Revision

Property 44 (R)

Current BACnet firmware revision used by the
controller

Protocol Version

Property 98 (R)

Current BACnet firmware protocol version

Default is Version 1

Protocol Revision

Property 139 (R)

Current BACnet firmware protocol revision

Default is Version 2

Max ADPU Length

Property 62 (R)

Maximum ADPU Length accepted

Default is 244

ADPU Timeout

Property 10 (R)

ADPU timeout value

Default is60 000 ms

Max_Master (R,W)

Maximum master devices allowed to be part of the
network. 0 to 127, default is 127