Viconics VZ7260(X) VZ7656(X) BACnet Installation Manual User Manual
Page 6

6
Device Object List for VZ7260 Models
Object Name
V
Z
72
60
F
5x
00
B
V
Z
72
60
C5
x0
0
B
O
b
jec
t P
ro
p
er
ty
O
b
jec
t Typ
e
Inst
ance
#
GUI Damper Position
X
R
AI
1
Cfg Zone MAC
X
X
R
AV
1
Cfg RTC MAC
X
X
R/W
AV
2
Cfg AO2 OA Lock Spt
X
R/W
AV
3
Cfg BO5 OA Lock Spt
X
X
R/W
AV
4
Cfg Damper Min Pos
X
X
R/W
AV
5
Cfg Damper Max Pos
X
X
R/W
AV
6
Cfg Damper Max Heat Pos
X
X
R/W
AV
7
Cfg Heating Stpt Limit
X
X
R/W
AV
8
Cfg Cooling Spt Limit
X
X
R/W
AV
9
Cfg Deadband
X
X
R/W
AV
10
GUI Occupied Heat Spt
X
X
R/W
AV
11
GUI Occupied Cool Spt
X
X
R/W
AV
12
GUI Unoccupied Heat Spt
X
X
R/W
AV
13
GUI Unoccupied Cool Spt
X
X
R/W
AV
14
GUI Stand-By Heat Spt
X
X
R/W
AV
15
GUI Stand-By Cool Spt
X
X
R/W
AV
16
GUI AO2 Status
X
R
AV
17
GUI UI3 Status
X
X
R
AV
18
GUI PI Heat Weighted Demand
X
X
R
AV
19
GUI PI Cool Weighted Demand
X
X
R
AV
20
GUI Room Temperature
X
X
R
AV
21
GUI Outdoor Temperature
X
X
R/W
AV
22
Cfg Device Instance
X
X
R
AV
23
GUI PI Heat Demand
X
X
R
AV
24
GUI PI Cool Demand
X
X
R
AV
25
Cfg Password
X
X
R/W
AV
26
Cfg Stand-by Time
X
X
R/W
AV
27
Cfg Unoccupied Time
X
X
R/W
AV
28
GUI Heating Performance
X
X
R
AV
29
GUI Cooling Performance
X
X
R
AV
30
Cfg BO3-BO4 OA Lock Spt
X
R/W
AV
31
GUI Room CO2 Level
X
X
R/W
AV
32
GUI Transferred CO2 Value
X
X
R/W
AV
33
GUI AI4 Value
X
X
R
AV
34
GUI BI1 Status
X
X
R
BI
1