VZ7656 List of Property Enumeration Sets for MV Objects

Object Name

Object

Type and

instance

BACnet Index

Text

Default value

Cfg RTC Baud

MV 1

1

9600 ( Bps )

Auto

2

19200 ( Bps )

3

38400 ( Bps )

4

76800 ( Bps )

5

Auto

Cfg Control Type

MV 2

1

Highest

AV_H3 /Average
of Highest 3
Zones

2

AV_H3 /Average of
Highest 3 Zones

3

AV_H5 /Average of
Highest 5 Zones

Cfg Local Keypad
Lockout

MV 3

1

Level 0 / No Lockout

Level 0 / No
Lockout

2

Level 1

3

Level 2

GUI Zone
Sequence

MV 4

1

Off / Never used

Cool

2

Cool

3

Heat

Cfg Static Pressure
Transducer Range

MV 5

1

0 to 1.5“ of WC

0 to 1.5“ of WC

2

0 to 2.0“ of WC

3

0 to 3.0“ of WC

4

0 to 4.0“ of WC

5

0 to 5.0“ of WC

Cfg Heating Stages

MV 6

1

1 Stage

2 Stages

2

2 Stages

Cfg Cooling Stages

MV 7

1

1 Stage

2 Stages

2

2 Stages

Cfg Heating CPH

MV 8

1

3 CPH

4 CPH

2

4 CPH

3

5 CPH

4

6 CPH

5

7 CPH

6

8 CPH

Cfg Cooling CPH

MV 9

1

3 CPH

4 CPH

2

4 CPH

Cfg Min. On/Off
Time
(Anticycle)

MV 10

1

0 minute

2 minutes

2

1 minute

3

2 minutes

4

3 minutes

5

4 minutes

6

5 minutes