Viconics VZ7260(X) VZ7656(X) BACnet Installation Manual User Manual
Page 24

24
VZ7656 List of Property Enumeration Sets for BI and BV objects
Object Name
Object Type and
instance
Inactive_Text
Active_Text
Default
value
GUI G Fan
BI 1
Off
On
N/A
GUI Y1 Cool
BI 2
Off
On
N/A
GUI Y2 Cool
BI 3
Off
On
N/A
GUI W1 Heat
BI 4
Off
On
N/A
GUI W2 Heat
BI 5
Off
On
N/A
GUI BI 1 Status
BI 6
Not Activated
Activated
Not Activated
GUI Aux Status
BI 7
Off
On
N/A
Sta Heating Stages Lockout
Status
BI 8
Not Activated
Activated
Not Activated
Sta Cooling Stages Lockout
Status
BI 9
Not Activated
Activated
Not Activated
Sta Service Alarm
BI 10
Off
On
Off
Sta Filter Alarm
BI 11
Off
On
Off
Sta Clock Alarm
BI 12
Off
On
Off
Sta Discharge Temp Alarm
BI 13
Off
On
Off
Sta Reversing Valve Status
BI 14
Off
On
Off
GUI Y2 Compressor
BI 15
Off
On
Off
GUI Y1 Compressor
BI 16
Off
On
Off
Sta Fresh Air Alarm
BI 17
Off
On
Off
Sta High CO2 Alarm
BI 18
Off
On
Off
Cfg Units
BV 1
°C / SI Units
°F / Imperial
Units
°F / Imperial
Units
Cfg Progressive Recovery
BV 2
Off
Active
Off
Sta Com Lost Status
BV 3
Down
Up
N/A
Cfg Aux Contact
BV 4
N.O.
N.C.
N.O.