beautypg.com

Min prs, Regulating valve response time, Pressure regulating mode – TeeJet 844-AB Sprayer Control User Manual

Page 14: Minimum pressure setting

background image

12

www.teejet.com

844-AB

Regulating valve response time

Operating conditions may require a higher or lower response speed

for the regulating valve. To change the response time number, use

the Plus or Minus keys to increase or decrease the number.

Any number between 0.0 and 9.9 may be selected (0=Slow; 9=Fast).

The default value is 9.5. The first digit establishes the speed for

coarse adjustments (when relatively far from the target rate). The

second digit establishes the speed for the fine adjustment (when

relatively close to the target rate). If the regulating valve is plumbed

in a bypass line, the valve speed number of 9.5 works well for most

applications.
Figure 40: Regulating valve actuating factor

RE6

1

2 3

4 5

6 7

8 9

10 11

12

ACT

9.5

(coarse)

(fine)

If the regulating valve is plumbed in the throttling position (supply

line), start with a valve speed of 3.0 and adjust the number according

to application requirements. Adjusting agitation volumes can often

assist the regulating valve operation. Press the Programme key to

accept the entry and advance to the next step.
NOTE: The speed value can be adjusted to optimize system

performance. If the valve tends to “search” for the

programmed application rate by cycling the pressure up and

down continuously, reduce the number until the “searching”

is minimal or eliminated. A higher number will increase the

valve response speed and increase the rate of adjustment.

Pressure regulating mode

Pressure regulating mode directs the 844-AB to the location of the

regulating valve plumbing. Once established, this value should not

change unless the regulating valve is physically moved to a new

plumbing location. For additional information about plumbing, refer to

the Plumbing and installation manual supplied with this kit.
The default value of bypass “BYP” indicates that the pressure

regulating valve is plumbed in a bypass line. If no changes are

necessary, press the Programme key to accept the value and

advance to the next step.
Figure 41: Pressure regulating mode (Bypass mode)

1

2 3

4 5

6 7

8 9

10 11

12

BYP

NOTE: Once the bypass mode is selected and the console is set to

“manual” mode, the pressure regulating valve should close

when the Plus key is pressed and open when the

Minus key is pressed.

If the pressure regulating valve has been plumbed into in a supply

line to the booms, it is considered a “throttling position”. Use the

Plus or Minus keys to change the displayed value to “THR”

(throttling mode). By doing this, the polarity that the console uses to

control the regulating valve will be reversed.
Figure 42: Pressure regulating mode (Throttling mode)

1

2 3

4 5

6 7

8 9

10 11

12

ThR

NOTE: Once the throttling mode is selected and the console is set

to “manual” mode, the pressure regulating valve should open

when the Plus key is pressed and close when the

Minus key is pressed.

Press the Programme key to accept the entry and advance to the

next step.

Minimum pressure setting

The Minimum pressure setting establishes the minimum pressure

the sprayer will regulate. When the vehicle slows down, the control

system will sometimes regulate the pressure so low that it falls below

the manufacturer’s recommended pressure for the spray nozzle. It

may also reduce system flow to the point where the flow meter will

stall.
To avoid these situations, the 844-AB can be programmed to avoid

regulating below the pressure established with this setting. If the

default setting of 0.7 bar is used, the pressure will not fall below 0.7

bar while spraying in automatic mode.
Use the Plus or Minus keys to adjust the value. Press the

Programme key to advance to the next programme step.
Figure 43: Minimum pressure setting

1

2 3

4 5

6 7

8 9

10 11

12

0.7

Bar

MiN

PRS