beautypg.com

Conf, Lpm -1- 3.0, Reference pressure – TeeJet 844-AB Sprayer Control User Manual

Page 13: Reference flow

background image

11

98-70007-EN R4

844-AB

Reference flow rate per section

AB mode – The flow rate for each section of the sprayer must be

input into the 844-AB console so that the necessary adjustments

can be made when boom sections are shut off. The console is

programmed to treat the left and right boom sections as symmetrical;

therefore the console treats the flow rate for the lower left section

(L1) identically to the flow rate of the lower right section (R1). The

flow rate entered for section 1 will serve as reference flow for L1 and/

or R1.
Figure 34: AB flow rate illustration

HC mode – The flow rate for a single nozzle must be input into the

844-AB console so that the necessary adjustments can be made

when boom sections are shut off. If several different nozzles are

mounted to spray on a face, they should be considered as ONE

nozzle and the total flow should be programmed.
Figure 35: HC flow rate illustration

1. Select section

Up to twelve preset flow configurations can be entered into the

844-AB. The presets are represented by the numbers “1-12” at the

bottom of the display. The arrow symbol indicates which preset is

being programmed.
Select which preset flow configuration to programme. Use the Plus

or Minus keys to toggle through the twelve presets.

Figure 36: Preset selection

SEL

ConF

1

2 3

4 5

6 7

8 9

10 11

12

Press the Auto/man key to setup the reference pressure and

reference flow of the selected preset.
Press the Programme key to advance to the next programme

step in System setup mode. It is not necessary to programme all

twelve presets unless they are to be used. Programme the number of

presets required. Press the Programme key again to continue in

System setup mode.

2. Reference pressure

Before entering the reference flow, determine the pressure at which

the flow will be referenced. Use the Plus or Minus keys to

adjust the value of the pressure Bar to be used as flow reference.

The pressure selected to reference flow is not critical (any pressure

can be used). Select a pressure that is close to normal operating

pressure or select a pressure from the flow rate chart for the nozzles

being used.
Figure 37: Reference pressure

REF

1

2 3

4 5

6 7

8 9

10 11

12

3.0

Bar

Press the Auto/man key to advance to the reference flow for

current preset section.

3. Reference flow

Calculate (add) the flow rates at the referenced pressure from all

nozzles on the current preset section (left or right should be the

same). Enter the total flow rate in litres/min. for the current preset

section. Use the Plus or Minus keys to adjust the value.
Figure 38: Reference flow (Section one entry)

1.36

1

2 3

4 5

6 7

8 9

10 11

12

LPm

-1-

3.0

Bar

Press the Auto/man key to return to the select section option.

Next section

Repeat steps 1-3 for all sections as needed.
Figure 39: Reference flow (Section two entry)

0.85

1

2 3

4 5

6 7

8 9

10 11

12

LPM

-1-

3.0

Bar

Once programming is complete for all presets, press the

Programme key to advance to the next programming step.