beautypg.com

Reznor SFT Unit Installation Manual User Manual

Page 12

background image

Form RZ -NA-I-SFT, Mfg No. 173474 (Rev 6), Page 11

7C

Slide combustion air inlet
over the vent pipe and fasten
to the end of the combustion
air pipe.

Install field-
supplied
flashing at
roof opening.

3. Attach the concentric adapter. Insert the
vent pipe and combustion air pipe up
through the roof and secure the adapter box.
Flash the combustion air pipe to the out-
side of the roof as required.

Seal top joint
(between the vent
pipe and air inlet)
with silicone.

4. Slide the combustion air in-
let over the vent pipe
and fas-
ten collar to the end of the com-
bustion air pipe with sheetmetal
screws (See Figure 7C). Seal
joint at top between vent pipe
and combustion air inlet with
silicone sealant to prevent wa-
ter leakage.

9-3/8”

(238mm)

6 ft (1829mm) minimum

12” (305mm)

Wall or

Adjoining

Building

11” (279mm)

Flashing

(field

supplied)

Roof

18”(457mm)

minimum 5 ft (1524mm)

maximum (Size

according to

anticipated

snow depth.)

Thimble

Concentric

Adapter

Vent Pipe - A minimum of 12”

(305mm) of straight pipe is

recommended between the

heater outlet and the elbow.

See No 4, page 7,

for requirements

and use of taper-

type connectors.

7) Connect Concentric Adapter to the Heater - Use the pipe
specified and joints required for type of pipe. If collars at the
heater or the collar or opening on the adapter are different diam-
eters from the pipe (use only diameters listed on page 7), make
joints with field-supplied taper-type reducer or increaser.
A minimum of 12" (305 mm) of straight pipe is required at the
venter outlet.
Due to the high temperature, do not enclose the exhaust pipe or
place pipe closer than 6" (152 mm) to combustible material.
Installation of the vertical vent and combustion air system on your
separated-combustion unit is complete.

Figure 7E - Installation of Separated-Combustion Unit with Vertical Vent and Combustion Air Pipes (Option CC2)

Rear View

Side View

"Through-the-Roof" View of a

typical installation of a vertical vent/

inlet air terminal and concentric

adapter (Option CC2)

Exhaust
Terminal

7D

12" (305mm)

minimum

5. Attach the exhaust ter-
minal
with sheetmetal
screws (See Figure 7D).

6. Vertical vent terminal/
combustion air inlet is in-
stalled and ready for con-
nection to the heater.

Refer to Figure7E and
verify that all installation
requirements are met.

Snow

Clearance

7B

22"

(559mm)

minimum

Vent

Termina

l

Flue

Exhaust

(Vent )

Pipe

Seal with high

temperature silicone

rubber sealant supplied

with the kit.

Combustion

Air Inlet

Flashing

(field

supplied)

Roof

Combustion

Air Pipe

Concentric

Adapter

Vent Pipe

(See

requirements

on page 7.)

Combustion

Air Pipe

(See requirements

on page 7.)