beautypg.com

Q6sp charging charts - cooling only – Reznor Q6SP Unit Installation Manual User Manual

Page 26

background image

26

Q6sP charging charts - cooling only

application notes on the use of charging charts

This equipment’s cooling systems contain refrigerant under

high pressure, always use safe practices when servicing

the unit. Always review the factory literature and safety

warnings prior to servicing.

All Q6SP-090/120 units are shipped from the factory with

the proper amount and type of refrigerant. Always inspect

the unit rating label to determine the units information prior

to working on the system. Do not mix different refrigerants

or charge the unit with a refrigerant not listed on the unit

rating label.

The charging charts below are valid for a variety of indoor,

return air conditions and are most highly influenced by

the outdoor ambient temperature, outdoor fan operation

and the unit operating voltage. Before referencing the

charts below, always ensure that all compressor circuits

are energized and have stable operation. As can be seen

in the charging charts, the ideal system sub-cooling can

vary over the range of operation. Always reference the

charts to determine the ideal amount of sub-cooling for

a given liquid pressure. Units charged to other values will

not perform at the rated unit efficiency (EER) or rated

Coefficient of Performance (COP) in heating mode.

To inspect a systems operation, using quality instruments,

match the measured liquid temperature to the units chart.

The measured liquid pressure reading should be within

3% of the value shown for most installations. For two stage

systems, the charts are valid for both compressor stages.

For systems that are operating with more then a 5%

deviation, inspect the unit for the proper voltage and phase

balance and the refrigeration system for leaks.

Units that are operating at less then 95% of the nominal

voltage or with a 2% phase imbalance may see a more

significant deviation then the amount stated above.

Always use safe and environmentally sound methods for

refrigerant handling. When repairing system leakages,

always utilize a nitrogen (inert) gas to protect the refrigerant

system and pressure check the repair before re-charging.

Always replace the filter-dryers when performing any

repair to the refrigeration system with one capable of

acid removal. After completing the repairs, evacuate the

system to 350-500 microns and weight in the refrigerant

to the amount specified on the unit rating label.

Do not use these charts for two stage systems operating only under a single stage call for cooling.

Do not use these charts in systems that do not have all the outdoor fans energized, or have the fans cycling

under a low-ambient control. Refer to the low-ambient kit instructions for more information, if applicable.