Electrical data – Reznor Q6SP Unit Installation Manual User Manual
Page 17

17
ElEctrIcal Data
Model
number
Q6sP-
(see notes 2 & 3)
nominal
unit
Voltage
(see note 1)
High
static
Kit #
compressors
outdoor
motors
(2) ea.
Indoor Motor
(see note 4)
total
unit
rla
unit only
circuit
Qty
rla
lra
Fla
Hp
Fla
rla
Mca
MoP
Factory unit Electrical Data
-090Ca
208 - 230 V
Factory Std.
2 ea.
13.1
83.1
2.3
1
3.2 - 3.1
34.1
37 - 37
50 - 50
-090Da
460 V
2 ea.
6.1
41
1.2
1.5
16.1
18
20
-120Ca
208 - 230 V
Factory Std.
2 ea.
15.6
110
2.3
1.5
4.4 - 4.2
40.3
44 - 44
50 - 50
-120Da
460 V
2 ea.
7.8
52
1.2
2.1
20.1
22
25
Medium & High static Drive Electrical Data
-090Ca
208 - 230 V
921646
2 ea.
13.1
83.1
2.3
1.5
4.4 - 4.2
35.3
39 - 38
50 - 50
-090Da
460 V
2 ea.
6.1
41
1.2
2.1
16.7
18
20
-090Ca
208 - 230 V
921647
2 ea.
13.1
83.1
2.3
2
6.0 - 5.8
36.9
40 - 40
50 - 50
-090Da
460 V
2 ea.
6.1
41
1.2
2.9
17.5
19
25
-120Ca
208 - 230 V
921645
2 ea.
15.6
110
2.3
2
6.0 - 5.8
41.9
46 - 46
60 - 60
-120Da
460 V
2 ea.
7.8
52
1.2
2.9
20.9
23
30
table 2a. Q6sP Electrical Data - Multiple supply circuits / unit only
H5HK
Heater Kit
Model #
(see note 6)
Electric Heat Kit (Field Installed with Multiple circuit Kit # 917468)
Electrical Data table - Heater onlY
nominal
Heater
kW
line
Voltage
actual
Heater
kW
Heater amps
(line)
Heater only circuit
Mca
MoP
009Q-01
9
208 / 240
6.76 / 9.0
18.76 / 21.65
23.5 / 27.1
25 / 30
018Q-11
18
208 / 240
13.07 / 17.4
36.28 / 41.86
45.3 / 52.3
50 / 60
030Q-22
30
208 / 240
21.63 / 28.80
60.0 / 69.3
75.1 / 86.6
80 / 90
035Q-22
35
208 / 240
26.1 / 34.8
72.55 / 83.72
90.7 / 104.6
100 / 110
009S-01
9
480
9.9
11.91
14.9
15
018S-01
18
480
18
21.65
27.1
30
030S-01
30
480
28.8
34.64
43.3
45
035S-01
35
480
34.8
41.86
52.3
60
notEs:
1) To achieve the rated unit performance, unit voltage should be within 2% of nominal.
2) For C series units:
Nominal Unit Input Voltage = 208-230 Volt, 60 Hertz, 3 Phase
Minimum allowed unit voltage = 187V
Maximum allowed voltage = 253V
3) For D series units:
Nominal Unit Input Voltage = 460 Volt, 60 Hertz, 3 Phase
Minimum allowed unit voltage = 414V
Maximum allowed voltage = 506V
4) Indoor Motors meet 2010 DOE requirements (Premium Efficient)
5) Refer to High Static Drive Kit Installation Instructions for additional information
6) Refer to H5HK Kit Installation Instructions for additional information
7) FLA = Full Load Amps
MCA = Minimum Circuit Ampacity
RLA = Rated Load Amps
MOP = Maximum Over-Current Protection
LRA = Locked Rotor Amps
8) Refer to table 3 for single circuit MCA/MOP data
table 2b. H5HK Electrical Data - Multiple supply circuits