Q6sp-090(c/d)a – Reznor Q6SP Unit Installation Manual User Manual
Page 23

23
Q6sP-090(c/D)a
Factory Standard: 1Hp Horizontal Performance Chart
‡ Indicates Factory Sheave Setting for Pre-configured Units
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Turn
Open
1
Turn
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open
3
Turns
Open
3.5
Turns
Open ‡
4
Turns
Open
4.5
Turns
Open
5
Turns
Open
5.5
Turns
Open
6
Turns
Open
0.1
CFM
3638
3456
3288
3119
RPM
579
556
535
514
kW
0.86
0.77
0.69
0.61
0.2
CFM
3720
3548
3354
3160
2975
2789
RPM
626
603
581
558
537
516
kW
0.97
0.87
0.78
0.69
0.62
0.55
0.3
CFM
3623
3441
3259
3049
2839
2635
2430
RPM
651
628
605
583
560
540
519
kW
1.00
0.89
0.79
0.71
0.63
0.55
0.48
0.4
CFM
3550
3352
3147
2942
2710
2478
2231
RPM
671
654
631
607
585
563
542
kW
1.03
0.92
0.82
0.72
0.64
0.56
0.48
0.5
CFM
3482
3280
3077
2833
2589
2270
RPM
690
673
656
633
609
536
kW
1.06
0.94
0.83
0.73
0.64
0.55
0.6
CFM
3192
2964
2735
2421
RPM
692
676
659
635
kW
0.96
0.85
0.74
0.64
0.7
CFM
3148
2879
2566
2253
RPM
719
694
678
661
kW
0.99
0.86
0.75
0.63
0.8
CFM
3108
2808
2509
RPM
744
721
696
kW
1.04
0.89
0.76
0.9
CFM
2712
2312
RPM
747
723
kW
0.92
0.75
1.0
CFM
RPM
kW
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil.
When utilized with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kits
table 6. Blower Performance for Q6sP-090(c,D)a series
(7.5 ton Horizontal Models only)