Q6sP-090(c/D)a

Factory Standard: 1Hp Horizontal Performance Chart

‡ Indicates Factory Sheave Setting for Pre-configured Units

External

Unit

Static

(in-Wg)

Operating

@ 230 or

460 Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns
Open

2

Turns
Open

2.5

Turns
Open

3

Turns
Open

3.5

Turns

Open ‡

4

Turns
Open

4.5

Turns
Open

5

Turns
Open

5.5

Turns
Open

6

Turns
Open

0.1

CFM

3638

3456

3288

3119

RPM

579

556

535

514

kW

0.86

0.77

0.69

0.61

0.2

CFM

3720

3548

3354

3160

2975

2789

RPM

626

603

581

558

537

516

kW

0.97

0.87

0.78

0.69

0.62

0.55

0.3

CFM

3623

3441

3259

3049

2839

2635

2430

RPM

651

628

605

583

560

540

519

kW

1.00

0.89

0.79

0.71

0.63

0.55

0.48

0.4

CFM

3550

3352

3147

2942

2710

2478

2231

RPM

671

654

631

607

585

563

542

kW

1.03

0.92

0.82

0.72

0.64

0.56

0.48

0.5

CFM

3482

3280

3077

2833

2589

2270

RPM

690

673

656

633

609

536

kW

1.06

0.94

0.83

0.73

0.64

0.55

0.6

CFM

3192

2964

2735

2421

RPM

692

676

659

635

kW

0.96

0.85

0.74

0.64

0.7

CFM

3148

2879

2566

2253

RPM

719

694

678

661

kW

0.99

0.86

0.75

0.63

0.8

CFM

3108

2808

2509

RPM

744

721

696

kW

1.04

0.89

0.76

0.9

CFM

2712

2312

RPM

747

723

kW

0.92

0.75

1.0

CFM
RPM

kW

Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil.
When utilized with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kits

table 6. Blower Performance for Q6sP-090(c,D)a series

(7.5 ton Horizontal Models only)