Q6sp-090(c/d)a – Reznor Q6SP Unit Installation Manual User Manual

Page 22

background image

22

Q6sP-090(c/D)a

Factory Standard: 1Hp Down-flow Performance Chart

‡ Indicates Factory Sheave Setting

External

Unit

Static

(in-Wg)

Operating

@ 230 or

460 Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns
Open

2

Turns
Open

2.5

Turns
Open

3

Turns
Open

3.5

Turns

Open ‡

4

Turns
Open

4.5

Turns
Open

5

Turns
Open

5.5

Turns
Open

6

Turns
Open

0.1

CFM

3780

3612

3444

3268

3092

RPM

602

580

558

536

513

kW

0.92

0.83

0.75

0.69

0.63

0.2

CFM

3717

3545

3361

3177

2979

2781

RPM

624

604

583

561

538

515

kW

0.96

0.86

0.77

0.69

0.63

0.57

0.3

CFM

3644

3465

3286

3077

2867

2635

2402

RPM

648

627

606

585

564

541

518

kW

0.99

0.89

0.79

0.70

0.62

0.56

0.50

0.4

CFM

3542

3356

3156

2956

2726

2495

2212

RPM

672

651

630

609

588

566

544

kW

1.01

0.90

0.81

0.71

0.63

0.54

0.48

0.5

CFM

3487

3270

3053

2834

2615

2321

RPM

697

675

653

632

611

590

kW

1.05

0.93

0.82

0.73

0.63

0.54

0.6

CFM

3412

3181

2945

2709

2428

RPM

717

698

677

656

635

kW

1.07

0.95

0.84

0.74

0.64

0.7

CFM

3131

2849

2557

2264

RPM

719

704

682

659

kW

0.97

0.85

0.74

0.63

0.8

CFM

3003

2783

RPM

744

721

kW

0.99

0.87

0.9

CFM

2631

2337

RPM

748

723

kW

0.87

0.74

1.0

CFM
RPM

kW

Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
When utilized with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kit

table 5. Blower Performance for Q6sP-090(c,D)a series

(7.5 ton Downflow Models only)