Q6sp-090(c/d)a – Reznor Q6SP Unit Installation Manual User Manual
Page 22

22
Q6sP-090(c/D)a
Factory Standard: 1Hp Down-flow Performance Chart
‡ Indicates Factory Sheave Setting
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Turn
Open
1
Turn
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open
3
Turns
Open
3.5
Turns
Open ‡
4
Turns
Open
4.5
Turns
Open
5
Turns
Open
5.5
Turns
Open
6
Turns
Open
0.1
CFM
3780
3612
3444
3268
3092
RPM
602
580
558
536
513
kW
0.92
0.83
0.75
0.69
0.63
0.2
CFM
3717
3545
3361
3177
2979
2781
RPM
624
604
583
561
538
515
kW
0.96
0.86
0.77
0.69
0.63
0.57
0.3
CFM
3644
3465
3286
3077
2867
2635
2402
RPM
648
627
606
585
564
541
518
kW
0.99
0.89
0.79
0.70
0.62
0.56
0.50
0.4
CFM
3542
3356
3156
2956
2726
2495
2212
RPM
672
651
630
609
588
566
544
kW
1.01
0.90
0.81
0.71
0.63
0.54
0.48
0.5
CFM
3487
3270
3053
2834
2615
2321
RPM
697
675
653
632
611
590
kW
1.05
0.93
0.82
0.73
0.63
0.54
0.6
CFM
3412
3181
2945
2709
2428
RPM
717
698
677
656
635
kW
1.07
0.95
0.84
0.74
0.64
0.7
CFM
3131
2849
2557
2264
RPM
719
704
682
659
kW
0.97
0.85
0.74
0.63
0.8
CFM
3003
2783
RPM
744
721
kW
0.99
0.87
0.9
CFM
2631
2337
RPM
748
723
kW
0.87
0.74
1.0
CFM
RPM
kW
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
When utilized with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kit
table 5. Blower Performance for Q6sP-090(c,D)a series
(7.5 ton Downflow Models only)