beautypg.com

Q6sp-120(c/d)a – Reznor Q6SP Unit Installation Manual User Manual

Page 25

background image

25

Q6sP-120(c/D)a

Factory Standard: 1.5Hp Horizontal Performance Chart

‡ Indicates Factory Sheave Setting for Pre-configured Units

External

Unit

Static

(in-Wg)

Operating

@ 230 or

460 Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns
Open

2

Turns
Open

2.5

Turns

Open ‡

3

Turns
Open

3.5

Turns
Open

4

Turns
Open

4.5

Turns
Open

5

Turns
Open

5.5

Turns
Open

6

Turns
Open

0.1

CFM

4425

4303

4157

4011

3878

3745

RPM

688

671

653

635

617

599

kW

1.44

1.33

1.23

1.12

1.04

0.95

0.2

CFM

4366

4227

4087

3951

3815

3665

3515

RPM

707

690

672

655

637

619

601

kW

1.48

1.36

1.25

1.15

1.05

0.97

0.88

0.3

CFM

4278

4137

3994

3850

3694

3537

3369

3201

RPM

725

709

692

674

656

638

620

602

kW

1.50

1.39

1.28

1.17

1.07

0.98

0.89

0.80

0.4

CFM

4198

4061

3923

3763

3602

3425

3248

3071

RPM

743

727

711

694

676

658

640

623

kW

1.52

1.41

1.30

1.19

1.09

0.99

0.89

0.81

0.5

CFM

3969

3816

3662

3490

3318

3127

RPM

746

729

712

695

677

660

kW

1.44

1.32

1.20

1.10

0.99

0.89

0.6

CFM

3851

3719

3543

3366

3181

2996

RPM

764

749

732

714

698

681

kW

1.44

1.33

1.22

1.11

1.00

0.90

0.7

CFM

3749

3594

3438

3232

3026

RPM

781

767

752

734

716

kW

1.44

1.33

1.22

1.11

1.00

0.8

CFM

3614

3487

3298

3109

RPM

795

785

771

756

kW

1.44

1.34

1.22

1.10

0.9

CFM

3515

3352

3184

2946

RPM

813

801

789

773

kW

1.43

1.32

1.21

1.09

1.0

CFM

3218

2993

RPM

816

805

kW

1.31

1.18

Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil.
When utilized with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kits

table 8. Blower Performance for Q6sP-120(c,D)a series

(10 ton Horizontal Models only)