beautypg.com

Q6sp-120(c/d)a – Reznor Q6SP Unit Installation Manual User Manual

Page 24

background image

24

Q6sP-120(c/D)a

Factory Standard: 1.5Hp Down-flow Performance Chart

‡ Indicates Factory Sheave Setting

External

Unit

Static

(in-Wg)

Operating

@ 230 or

460 Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2

Turn

Open

1

Turn

Open

1.5

Turns
Open

2

Turns
Open

2.5

Turns

Open ‡

3

Turns
Open

3.5

Turns
Open

4

Turns
Open

4.5

Turns
Open

5

Turns
Open

5.5

Turns
Open

6

Turns
Open

0.1

CFM

4468

4349

4230

4086

3942

3804

3665

RPM

706

689

672

653

633

616

599

kW

1.54

1.43

1.32

1.23

1.14

1.04

0.93

0.2

CFM

4412

4244

4124

4003

3847

3690

3546

3402

RPM

725

708

691

674

655

635

618

601

kW

1.58

1.44

1.34

1.24

1.15

1.06

0.96

0.86

0.3

CFM

4192

4042

3888

3733

3589

3445

3287

3129

RPM

727

710

693

676

657

637

620

603

kW

1.49

1.36

1.26

1.15

1.07

0.99

0.89

0.78

0.4

CFM

4106

3951

3796

3631

3466

3316

3165

2993

RPM

745

729

712

695

678

659

639

623

kW

1.51

1.39

1.27

1.17

1.08

0.99

0.91

0.81

0.5

CFM

3998

3871

3706

3540

3368

3196

3017

RPM

761

747

731

714

697

680

661

kW

1.51

1.42

1.30

1.18

1.09

0.99

0.90

0.6

CFM

4016

3903

3760

3616

3428

3240

3052

RPM

791

777

763

749

733

716

700

kW

1.59

1.49

1.41

1.32

1.20

1.09

0.98

0.7

CFM

3903

3801

3693

3512

3330

3118

RPM

806

793

779

766

752

736

kW

1.59

1.48

1.39

1.31

1.23

1.10

0.8

CFM

3654

3542

3406

3214

3022

RPM

808

795

781

768

754

kW

1.49

1.38

1.27

1.19

1.11

0.9

CFM

3356

3232

3074

RPM

810

797

783

kW

1.36

1.26

1.15

1.0

CFM

3013

RPM

812

kW

1.21

Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil.
When utilized with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kits

table 7. Blower Performance for Q6sP-120(c,D)a series

(10 ton Downflow Models only)