beautypg.com

Warning – Reznor SDH Option - Installation - Venting Instructions User Manual

Page 7

background image

Form I-SDH-V, P/N 211410 R5, Page 7

TABLE 4 - Parts in

the Horizontal Vent/

Combustion Air

Terminal Package

(Option CC6)

Qty Sizes

P/N

Description

1

75-125

211762 Complete Horizontal Vent/Combustion Air Terminal Kit (Same

as Option CC6)

150-400A

211763

1

75-125

211789 Concentric Adapter Box (NOTE: Refer to

FIGURE 5, page 5,

and verify diameter of vent pipe opening.)

150-400A

211790

1

75-125

211791

Exhaust Grill

150-400A

211792

1

75-125

151755

Inlet Guard

150-400A

124940

8

75-400A

37661

#10-16 x 1/2" long Screws to attach the exhaust grill and the

inlet guard

2

75-400A

207232 Brackets for attaching Concentric Adapter Box (See FIGURE

11, page 8.)

1

75-400A

53335

Tube of High Temperature (450°F) Silicone Sealant

Installation Instructions

for Horizontal Kit

Option CC6

(in compliance with

requirements on

pages 2-6)

1. Determine the location on the outside wall for the vent terminal. Location

must comply with vent length requirements, Requirement No. 2 on page 2. In most

applications, the terminal would be on a level with the heater mounting height. Allow

1/4” per foot (6mm per 305mm) downward pitch for condensate drain.
Minimum clearances for the horizontal vent terminal are shown in

TABLE 5. Also,

select a location that complies with adjoining building clearances as shown in

FIGURE 12, pages 8-9.

Products of combustion can cause discoloring of some building finishes and

deterioration of masonry materials. Applying a clear silicone sealant that is normally

used to protect concrete driveways can protect masonry materials. If discoloration is

an esthetic problem, re-locate the vent or install a vertical vent.

WARNING

All vent terminals must be positioned or located away from fresh air intakes,

doors and windows to preclude combustion products from entering occupied

space. Failure to comply could result in severe personal injury or death and/

or property damage.

TABLE 5 - Clearances

to Horizontal Vent

Terminal

Structure

Minimum Clearances for Vent Terminal Location (all

directions unless specified)

Forced air inlet within 10 ft (3.1M)*

3 ft (0.9M) above

Combustion air inlet of another appliance

6 ft (1.8M)

Door, window, or gravity air inlet (any build-

ing opening)

4 ft (1.2M) horizontally
4 ft (1.2M) below
1 ft (305mm) above

Electric meter, gas meter ** and relief

equipment

U.S. - 4 ft (1.2M) horizontally
Canada - 6 ft (1.8M)

Gas regulator **

3 ft (0.9M) horizontally

Adjoining building or parapet

6 ft (1.8M)

Adjacent public walkways

7 ft (2.1M) above

Grade (ground level)

3 ft (0.9M) above***

*Does not apply to the inlet of a direct vent appliance. **Do not terminate the vent directly

above a gas meter or service regulator. *** Consider local snow depth conditions. The vent

must be at least 6” (152mm) higher than anticipated snow depth.

2. Install the Vent Pipe and Combustion Air Pipe Runs - Use the type of pipe

specified in Requirement No. 1, page 2. Comply with Requirement No. 3, pages 2-3,

when attaching pipes to the heater. Length must comply with Requirement 2, page 2.

Seal all joints. Due to the high temperature,

do not enclose the exhaust pipe or place

pipe closer than 6” (152 mm) to combustible material. Extend the runs close to the

wall location selected in Step 1 and comply with Requirement No. 6, page 4.