beautypg.com

Venting requirements (cont’d) – Reznor SDH Option - Installation - Venting Instructions User Manual

Page 4

background image

Form I-SDH-V, P/N 211410 R5, Page 4

Venting

Requirements

(cont’d)

FIGURE 3 - STEP 2

Insert the pipe prepared with sealant

into the inner pipe of the double-wall

pipe until the bead of sealant contacts

the inner pipe creating a sealed joint.

FIGURE 3 - STEP 3

Spaced equally around the double-wall

pipe, drill three small holes below the

sealant ring. Insert 3/4 inch long sheet-

metal screws to secure the joint. Do not

overtighten screws.

Single-Wall with

Sealant (STEP 1)

Double-Wall Pipe

6. Clearance

Do not enclose the vent pipe or place pipe closer than 6” (152mm) to combustible

material.

5. Support

Support horizontal run every six feet (1.8M). Support vertical run of Category III vent

pipe in accordance with the requirements of the pipe manufacturer. Support vertical

single-wall pipe in accordance with accepted industry practices. Do not rely on the

heater or the adapter box for support of either horizontal or vertical pipes. Use non-

combustible supports on vent pipe.
NOTE: The vertical vent double-wall vent terminal pipe does not attach to the concen-

tric adapter box and must be supported during installation.

All separated combustion installations

require a concentric adapter box as illustrated

in

FIGURE 4. The concentric adapter box is included in the vent/combustion air ter-

minal kit. Installation instructions depend on whether the vent terminal is horizontal

(Option CC6) or vertical (Option CC2).

8. Concentric Adapter

Box

FIGURE 4 - A Concentric

Adapter Box is a Required

Part of all Model SDH

Installations

Collar for attaching

outside concentric

portion of the

combustion air pipe

A vent/combustion air kit which includes the concentric

adapter box is ordered with the heater. A horizontal

terminal vent/combustion air kit is Option CC6; a

vertical terminal vent/combustion air kit is Option CC2.

Collar for connecting indoor portion of the

combustion air pipe

Opening for exhaust vent pipe to pass through

the box. (See NOTE in FIGURE 5.)

View of Vent Terminal

Connection Side

On all Model Sizes, any length of single-wall vent pipe exposed to cold air or run

through an unheated area or an area with an ambient temperature of 45°F or less must

be insulated along its entire length with a minimum of 1/2” foil-faced fiberglass, 1-1/2#

density insulation.
Where extreme conditions are anticipated, install a means of condensate disposal.

7. Condensation

The illustrations in

FIGURE 5 and FIGURE 6 apply to the concentric adapter box in

both the horizontal terminal vent/combustion air kit (Option CC6) and the vertical ter-

minal vent/combustion air kit (Option CC2). All dimensions are the same except for the

opening for the vent pipe (See

NOTE in FIGURE 5).

Instructions for Attaching the Terminal-End Double-Wall (Type -B)

Section of the VERTICAL Vent Pipe (Applies only to Option CC2

installation) (cont’d)

4. Joints and Sealing (cont’d)

View of Heater

Connection Side

FIGURE 3 (cont’d) -

Follow STEPS to join

Double-Wall (Type B)

Pipe (VERTICAL VENT

Option CC2 ONLY) to

Single-Wall Pipe, to

Category III Pipe, or to

a Taper-type Connector