beautypg.com

Warning – Reznor SDH Option - Installation - Venting Instructions User Manual

Page 10

background image

Form I-SDH-V, P/N 211410 R5, Page 10

1. Determine the location of the vent terminal.

Select a location away from fresh air intakes, allowing space for the concentric

adapter box inside. Vent terminal must be located from adjacent buildings as shown

in

FIGURE 17, page 12.

TABLE 7 - Minimum

Spacing Required for

More Than One Vertical

Vent/Combustion Air

Terminal (Option CC2)

2. Install the Vent Pipe and Combustion Air Pipe Run - Use the type of

pipe specified in Requirement No. 1, page 2, and comply with the attachment

requirements in Requirement No. 3, pages 2-3. Length must comply with

Requirement No. 2, page 2.
Seal all joints. Due to the high temperature,

do not enclose the exhaust pipe or place

pipe closer than 6” (152 mm) to combustible material. Provide supports for the pipes.

Extend the runs to close to the roof at the location selected in Step 1.
3. Prepare a clearance hole through the roof for the combustion air pipe -- a 6”

(152mm) diameter pipe for Sizes 75-125 or an 8” (203mm) diameter pipe for Sizes

150-400A. A thimble may or may not be required depending on building construction

and/or local codes. The larger diameter combustion air pipe serves as clearance for

the vent pipe on non-combustible construction.
4. Prepare the Concentric Adapter Box

a) Attach the brackets to the box. Follow the instructions in FIGURE 13.

Minimum Outdoor Design

Temperature

Minimum Spacing between Centerlines of Vent Pipes in

Vertical Combustion Air/Vent Terminals (Option CC2)

°F

°C

inches

mm

31 or warmer

0 or warmer

36

914

-10 to 30

-23 to -1

60

1524

less than -10

less than -23

84

2134

FIGURE 13 - Brackets

for Attaching the

Concentric Adapter Box

to the Roof

1) Attach the Brackets to the Box - The 6” (152mm)

portion of each bracket is designed with five 7/32”

diameter holes so that attachment to the box can

be adjusted.

If the roof is combustible, position brackets to allow for a

2” (51mm) clearance between the box and the roof. After

careful positioning, use sheetmetal screws to attach the

brackets. NOTE: If any holes are made in the box in error,

they must be sealed.

2) Attach the Box to the Roof (Step 5)

When the box is attached to the roof in Step 5, use

the 2-1/2” (64mm) portion of the brackets. To adjust to

construction each bracket has three 7/32” diameter holes.

b). Attach the outside portion of the combustion

air pipe to the box. Determine the length of the

combustion air pipe so that dimension ”X” in

FIGURE 14

is equal to the bracket length, plus the roof thickness,

plus anticipated snow depth, but does not exceed 48”

(1219mm) or have less than 18” (457mm) of pipe above

the roof. Attach the inlet air pipe to the collar of the

concentric adapter box with sheetmetal screws.
5. Attach the concentric adapter box to the roof. On

the inside, insert the combustion air pipe up through the

opening and attach brackets to the roof. (See

FIGURES

13, 14, and 15.) On the outside, flash the combustion air

pipe to the roof. Flashing is field supplied

.

6. Determine the length and install the double-wall

vent pipe.

a) Determine minimum length of the continuous

section of double -wall vent pipe (no joints). See

FIGURE 14. The vent pipe extending through the box

and concentric through the inlet air pipe and at least 3”

(76mm) higher

must be one piece of double-wall vent

pipe with no joints.

WARNING

All vent terminals must be positioned or located away from fresh

air intakes, doors and windows to preclude combustion products

from entering occupied space. Failure to comply could result in

severe personal injury or death and/or property damage

.

If more than one vertical concentric vent/combustion air terminal (Option CC2) is being

installed, the minimum spacing between vent centerlines is determined by the mini-

mum outdoor design temperature.

Installation Instructions

for Vertical Vent/

Combustion Air

Terminal Kit Option

CC2 (in compliance with

requirements, pages 2-6)

VERTICAL TERMINAL

INSTRUCTIONS -

Option CC2 (cont’d)