Form I-SDH-V, P/N 211410 R5, Page 6

Venting Requirements (cont’d)

7. Concentric Adapter Box (cont’d)

Model SDH 150 - Pipe Diameters and Connections

Required at the Concentric

Adapter Box

Concentric

Adapter

Box

8” (203mm) diameter

single-wall

inlet air pipe

5” (127mm) diameter

single-wall inlet air pipe

attaches to the heater

.

5” (127 mm) diameter single-wall or Category III

vent pipe attaches to the heater.

5” (127mm) diameter

vent pipe (if vertical

vent terminal, pipe

must be double-wall)

Requires a 6”to 5” (152 to

127 mm) taper-type reducer.

Taper-type

Pipe Diameter

Increaser

Airflow

• Size 150 requires a 5” to

6” (127mm to 152mm)

taper-type increaser in the

combustion air pipe.

FIGURE 8 - Concentric

Adapter Box

Connections for Model

SDH Size 150

Horizontal Terminal, Option CC6,

instructions begin below.

Vertical Terminal, Option CC2,

instructions begin on page 9.

FIGURE 10 - Follow the

Instructions that apply to

the Vent/Combustion Air

Terminal being installed.

Is the Vent Terminal

HORIZONTAL OR

VERTICAL?

FIGURE 9 - Concentric

Adapter Box Connections for

Sizes 300, 350, and 400A

• Sizes 300, 350, and 400A

always require a 6” to 5” (152

to 127 mm) reducer in the vent

pipe.

Taper-

type

Pipe

Diameter

Reducer

Airflow

Model SDH 300, 350, and 400A - Pipe Diameters

and Connections Required at

the Concentric Adapter Box

Requires a 6 to 5 inch (152 to 127mm) taper-type

pipe diameter reducer a maximum of 6” (152mm)

from the concentric adapter box.

Concentric

Adapter Box

8” (203mm) diameter single-wall

inlet air pipe

6” (152mm) diameter

single-wall inlet air pipe

attaches to the heater

.

6” (152mm) diameter

single-wall or

Category III vent pipe

attaches to the heater

.

5” (127mm) diameter

vent pipe (if vertical

vent, pipe must be

double-wall)

HORIZONTAL

TERMINAL

INSTRUCTIONS -

Option CC6

Components Required -

Factory and Field

Field-supplied installation requirements:

• Vent pipes - see requirements, page 2

• Combustion air pipes - see requirements, page 2

• Taper-type vent pipe diameter reducers and/or increasers as required

• Thimble (a thimble is not required if wall is of non-combustible construction)

• Flashing

• Sheetmetal screws, tape, and sealant as required
Before beginning, verify that the kit is at the site and that all components are correct for

the installation. Be sure all required field-supplied parts are available.