Form I-SDH-V, P/N 211410 R5, Page 5

Concentric Adapter Box

in Kits for SDH Sizes 75-125

Concentric Adapter Box

in Kits for SDH Sizes 150-400A

Top View

Top View

Heater Side View

Heater Side View

4” dia.

Combustion

Air Collar

6” Combustion

Air Collar

Opening for

5” vent pipe

to pass through the box --

See TABLE on the left.

Opening

for 4” vent

pipe to pass through the

box - See TABLE, left.

2” (51mm)

2” (51mm)

6-1/32” (153mm)

6” dia Collar for

Combustion Air

8” dia Collar

for Combustion

Air

11”

(279mm)

3-5/8”

(92mm)

4-3/8”

(111mm)

11-3/32” (282mm)

(102mm)

3-1/16” (78mm)

14-1/4”

(362mm)

(127mm)

5-7/32”

(133mm)

5-9/32”

(134mm)

(102mm)

13-3/8” (340mm)

FIGURE 5 - Concentric

Adapter Box Dimensions

NOTE: Horizontal and

vertical kits do not use the

same adapter box. The only

difference is the diameter of

the opening in the box for

the vent pipe. A vertical vent

requires double-wall pipe

and a slightly larger opening

through the box. See table

below and P/N list on page 7

or page 9.

Diameter (inches) of Opening

for Vent Pipe
Size

75-125 150-400A

Horizontal 4-1/16"

5-1/16"

Vertical

4-21/32" 5-21/32"

Diameter (mm) of Opening for

Vent Pipe
Size

75-125 150-400A

Horizontal 103mm

129mm

Vertical

118mm

144mm

FIGURE 6 - Concentric

Adapter Box Airflow

End View

showing Airflow

Gray Arrows show

Flow of Combustion Air

Vent (exhaust gas) flows through

the field-supplied vent pipe

that extends straight through

the concentric adapter box.

(Collar for attaching indoor

combustion air pipe)

(Collar for attaching outdoor

combustion air pipe)

NOTE: Applies to both

horizontal and vertical

installations.

Pipe Connections

at the Concentric

Adapter Box

When pipe diameters differ, depending on direction of airflow, join the pipes with either

a taper-type reducer or increaser. Requirements vary depending on the size of the

heater; refer to

FIGURE 7, 8, or 9 to determine whether or not pipe diameters dif-

fer. Do

NOT make actual connections until after reading the instructions and length

requirements for installing the vent/combustion air terminal kit.

The requirement for

a reducer or increaser is the same for both vertical and horizontal terminals, but

the length of pipe required varies by installation.

FIGURE 7 - Concentric

Adapter Box

Connections for Model

SDH Sizes 75, 100, 125,

175, 200, 225, and 250

Model SDH 75, 100, 125, 175, 200, 225, and 250 - Pipe Diameters and

Connections Required at the Concentric Adapter Box

Concentric Adapter Box

“D” - diameter of the

single-wall inlet air pipe

that att

aches to the heater

.

“A” - diameter of vent pipe

(if vertical vent, pipe

must be double-wall)

“C”- diameter of single-wall inlet air pipe

“B” - diameter of the single-wall or

Category III vent pipe that attaches

to the heater.

• Pipe diameters do not differ.

Taper-type connectors are

not required for these sizes.

Pipe

Model SDH Sizes

75, 100, 125

175, 200, 225, 250

A

4" (102mm)

5" (127mm)

B

4" (102mm)

5" (127mm)

C

6" (152mm)

8" (203mm)

D

4" (102mm)

6" (152mm)