Pipe connections at the concentric adapter box, Figure 5 - concentric adapter box dimensions, Figure 6 - concentric adapter box airflow – Reznor SDH Option - Installation - Venting Instructions User Manual
Page 5

Form I-SDH-V, P/N 211410 R5, Page 5
Concentric Adapter Box
in Kits for SDH Sizes 75-125
Concentric Adapter Box
in Kits for SDH Sizes 150-400A
Top View
Top View
Heater Side View
Heater Side View
4 dia.
Combustion
Air Collar
6 Combustion
Air Collar
Opening for
5 vent pipe
to pass through the box --
See TABLE on the left.
Opening
for 4 vent
pipe to pass through the
box - See TABLE, left.
2 (51mm)
2 (51mm)
6-1/32 (153mm)
6 dia Collar for
Combustion Air
8 dia Collar
for Combustion
Air
11
(279mm)
3-5/8
(92mm)
4-3/8
(111mm)
11-3/32 (282mm)
4
(102mm)
3-1/16 (78mm)
14-1/4
(362mm)
5
(127mm)
5-7/32
(133mm)
5-9/32
(134mm)
4
(102mm)
13-3/8 (340mm)
FIGURE 5 - Concentric
Adapter Box Dimensions
NOTE: Horizontal and
vertical kits do not use the
same adapter box. The only
difference is the diameter of
the opening in the box for
the vent pipe. A vertical vent
requires double-wall pipe
and a slightly larger opening
through the box. See table
below and P/N list on page 7
or page 9.
Diameter (inches) of Opening
for Vent Pipe
Size
75-125 150-400A
Horizontal 4-1/16"
5-1/16"
Vertical
4-21/32" 5-21/32"
Diameter (mm) of Opening for
Vent Pipe
Size
75-125 150-400A
Horizontal 103mm
129mm
Vertical
118mm
144mm
FIGURE 6 - Concentric
Adapter Box Airflow
End View
showing Airflow
Gray Arrows show
Flow of Combustion Air
Vent (exhaust gas) flows through
the field-supplied vent pipe
that extends straight through
the concentric adapter box.
(Collar for attaching indoor
combustion air pipe)
(Collar for attaching outdoor
combustion air pipe)
NOTE: Applies to both
horizontal and vertical
installations.
Pipe Connections
at the Concentric
Adapter Box
When pipe diameters differ, depending on direction of airflow, join the pipes with either
a taper-type reducer or increaser. Requirements vary depending on the size of the
heater; refer to
FIGURE 7, 8, or 9 to determine whether or not pipe diameters dif-
fer. Do
NOT make actual connections until after reading the instructions and length
requirements for installing the vent/combustion air terminal kit.
The requirement for
a reducer or increaser is the same for both vertical and horizontal terminals, but
the length of pipe required varies by installation.
FIGURE 7 - Concentric
Adapter Box
Connections for Model
SDH Sizes 75, 100, 125,
175, 200, 225, and 250
Model SDH 75, 100, 125, 175, 200, 225, and 250 - Pipe Diameters and
Connections Required at the Concentric Adapter Box
Concentric Adapter Box
D - diameter of the
single-wall inlet air pipe
that att
aches to the heater
.
A - diameter of vent pipe
(if vertical vent, pipe
must be double-wall)
C- diameter of single-wall inlet air pipe
B - diameter of the single-wall or
Category III vent pipe that attaches
to the heater.
• Pipe diameters do not differ.
Taper-type connectors are
not required for these sizes.
Pipe
Model SDH Sizes
75, 100, 125
175, 200, 225, 250
A
4" (102mm)
5" (127mm)
B
4" (102mm)
5" (127mm)
C
6" (152mm)
8" (203mm)
D
4" (102mm)
6" (152mm)