Form I-SDH-V, P/N 211410 R5, Page 11

FIGURE 14 - Concentric Adapter Box, Outdoor Combustion Air Pipe, and Concentric Vent Pipe

Concentric

Adapter Box

Mounting Brackets

X = length of

combustion air pipe required

through and above the roof.

Height from box to top of inlet air

pipe must not exceed 48” (1219mm).

Minimum height above the roof is

18” (457mm) and must be higher

than anticipated snow depth.

FIRST, attach Combustion Air Pipe and Install the

Concentric Box
1)
Determine length (X) of pipe (see requirements on the left).
2) Attach the pipe to the collar on the box.
3) Attach the brackets to the roof.

V

ent Flow

22” (559mm) minimum

Cold Climate NOTE:

In geographic areas where

the design ambient is -10°F

or lower, this minimum

height is 34” (864mm).

Collar for Indoor Portion of

the Combustion Air Pipe

Double-Wall Vent Pipe -

Extend length of double-wall

vent pipe a maximum of 6”

(152mm) below the box.

After box is installed, install Concentric Vent Pipe. -

One piece of continuous double-wall pipe must extend from

a minimum of 3” (76mm) above the outer combustion air

pipe to a maximum of 6” (152mm) below the box. (NOTE:
Vent
pipe does not attach to the box; it must be supported.)
1) Calculate height (see requirements on the left).
2) Be sure vent flow marking on pipe is in the right direction.
3) Slide pipe through the box and the outer inlet air pipe.
4) Attach to vent run no more than 6” (152mm) from the
adapter box. See instructions in FIGURE 3, pages 3-4.

Vent pipe

extending

through the

box and the

combustion

air pipe MUST

be one continuous

piece of double-

wall vent pipe.

A second section

of double-wall pipe

is permitted, joining

the long continuous

piece of vent pipe a

minimum of 3” (76mm)

above the top of the

combustion air pipe.

3” (76mm)

minimum

If needed, add a second section of double-wall pipe to

comply with the height requirement on the left.

Determine the minimum length by adding the requirements. Starting at the bot-

tom, the maximum the vent pipe can extend below the box is 6” (152mm);

plus 6”

(152mm) through the box;

plus length of bracket extending above the box; plus the

width of the roof;

plus the height of the outside combustion air pipe above the roof;

plus a minimum of 3” (76mm) beyond the top of the inlet air pipe. Total is the mini-

mum length of the one-piece double-wall vent pipe section. If the actual piece of vent

pipe is longer, extend it higher above the combustion air pipe. Do not extend it more

than 6” (152mm) below the box.
b) Install the pipe. Being sure the pipe is in the proper flow direction, slide the end

into the box and out through the combustion air pipe. Position the vent pipe so that

the end is no more than 6” (152mm) below the box. The upper end should extend at

least 3” (76mm) above the combustion air pipe.

NOTE: The double-wall vent pipe

does not attach to the box. The installer must provide support.
Follow the instructions in

FIGURE 3, pages 3-4, for connecting the double-wall pipe

to the vent run (single-wall pipe, Category III pipe, or taper-type connector).
Seal the circumference of the pipe and the opening of the box with silicone sealant.

Seal the area around the pipe completely.
7. On the outside, if an additional section of double-wall pipe is needed (See

FIGURE 16), add it. Make joint according to the pipe manufacturer’s requirements.

When vent pipe is the required height,

slide the combustion air inlet over the vent

pipe and fasten the collar to the combustion air pipe with sheetmetal screws. Seal the

opening at the top between the vent pipe and the combustion air inlet with silicone

sealant to prevent water leakage.
8. Attach the exhaust (vent) cap. Follow the illustrated instructions in FIGURE 2,

page 3.
9. Attach the indoor combustion air pipe. Use sheetmetal screws to attach the

single-wall combustion air pipe run to the collar on the concentric adapter box. Seal

with tape or sealant. If installing a Model SDH Size 150, field-supplied taper-type 5”

to 6” (127mm to 152mm) reducer is required to connect the combustion air pipe to

the collar on the box. See

FIGURE 8, page 6.

Outside view with
concentric adapter box
attached to underside
of roof. Install field-
supplied flashing at
roof opening.

18” (457mm)

minimum

(or higher if

snow clearance

is needed)

(NOTE: Maximum

from concentric

adapter box is

48” (1219mm.)

Combustion

Air Pipe

FIGURE 15 - Slide

attached Combustion

Air Pipe up through the

Roof