beautypg.com

F aq – Reznor EFMA Unit Installation Manual User Manual

Page 24

background image

24

6.

F

AQ

6.1 Floor Heating System

Q.1: Can I cut the EFMA heating cable to shorten it?

A.1: NEVER. If the EFMA roll is too long, detach the excess cable from the mat and

spread it on the floor in regular loops identical to those on the mat. Keep the

minimum distance from the walls and between parallel runs of cable (radius

bending of at least 20 mm [¾”] for loops).

Q.2: What should I do before choosing the EFMA system that’s right for me?

A.2: Sketch a plan to determine the surface area. We can help optimize your work

plan. Fax it to us at 724-662-3957.

Q.3: How do I repair EFMA in case of a malfunction?

A.3: First, as a PREVENTIVE measure during installation, test the cable each

time as specified in the installation guide. Also complete the measures’ table.

However, in case of a malfunction, an authorized REZNOR repair person will

visit to LOCATE the fault and REPAIR it. It is recommended that you keep

spare ceramic tiles or flooring for this purpose.

Q.4: Are there other watt densities per square foot available?

A.4: No. REZNOR believes that 12W/sq. ft. is the best watt density to optimize

comfort and prevent floor overheating. Moreover, the 240V and 120V systems

provide equal heating power per square foot.

Q.5: Can I crisscross, overlap, or touch two heating cables together?

A.5: NEVER. This will cause overheating. Keep cables at least 76 mm (3”) apart.

Q.6: Can the cable be bent 90°?

A.6: Yes, but make sure the radius bending is at least 20 mm (¾”). Any bending

smaller than this may damage the cable.

6.2 Installation

Q.7: Can I install one EFMA system on top of another?

A.7: NEVER. The system will overheat. Heating power must not exceed 12W/ sq. ft.

(130W/sq. m).

Q.8: Can EFMA be used for exterior snow melting?

A.8: No. EFMA is designed to provide comfort and heating in indoor residential

applications only.

Q.9: Is a GFCI necessary?

A.9: A GFCI is required in the bathroom. It is recommended for all other rooms.

Q.10: Is a floor sensor necessary?

A.10: Yes, to control floor surface temperature so that it does not exceed the floor

covering’s maximum temperature tolerance. Even if it is not an obligation

to use a floor sensor when using the system with an ambient thermostat,

REZNOR recommends the use of a floor sensor.

Q.11: Can I connect two EFMA systems to the same thermostat?

A.11: Yes. You can even connect additional systems provided the connection is

parallel and total output does not exceed the thermostat’s capacities.

Q.12: What happens if the voltage applied is the wrong one?

A.12: Connecting a 120V product to a 240V/208V current will overheat the system

and lead to an overheating and failure. A 240V/208V productconnected to a