2.2 Insulation Test

Measure EFMA’s insulation resistance at each step using a megohmeter (Fig.

2.2) and record readings on the measures’ table (this label is available at the

opening of the product).

IMPORTANT!

For the warranty to be valid, fill out the measures’  table and ensure that the

10 readings have been correctly noted.

A qualified electrician must measure the system’s insulation resistance as follows:
• Use a calibrated megohmeter only;
• Measure insulation resistance at the free end of the cold lead, between the phase

conductor and ground;

cold lead

Fig. 2.2

CAUTION! Dangerous Test

• Write the reading in the measures’ table;
• This reading must be over 1,000,000 ohms;
• If the reading is under 1,000,000 ohms, stop work and contact REZNOR’s technical

specialists at 1 800 695-1901.