beautypg.com

Reznor UDBS Option - Installation - Separated Combustion Venting User Manual

Page 8

background image

Form I-UD-V-SC, PN195676R17, Page 8

Applies to: Residential or Commercial/Industrial Installation

NOTE: Only UDAS 30, 45, 60, 75, 100, and 125 are certified for residential use.

1.0 Venting and Combustion Air Requirements (cont’d)

1.8 Concentric Adapter Box (cont’d)

FIGURE 8 - Concentric Adapter Box Connections for Sizes 30, 45, and 60 using 4”

(102mm) diameter pipes and for all Sizes 75, 100, 125, 150, 175, 200, 225, and 250

Models UDAS and UDBS 30, 45,
and 60 - Pipe Diameters and
Connections Required at the
Concentric Adapter Box When

Using 4” (102mm) Diameter

Pipes from the Heater to the

Concentric Adapter
AND
Models UDAS and UDBS 75,
100, 125, 150, 175, 200, 225,

and 250 - Pipe Diameters and
Connections Required at the
Concentric Adapter Box

Concentric

Adapter Box

“B” = diameter of vent

pipe that att

aches to the

heater

. Type of pipe must

comply with requirement

s

on page 3.

“D” = diameter of the

single-wall inlet air pipe

that att

aches to the heater

.

“C” = diameter of single-wall inlet air pipe

“A” = diameter

of the vent pipe

(Type of vent pipe

must comply with

requirements on

page 3.)

• Pipe diameters

do not differ.

Model UDAS and UDBS Sizes

A

B

C

D

30, 45, 60 with 4” vent and combustion air

runs from heater to concentric adapter box

inches

4

4

6

4

mm

102

102

152

102

75, 100, 125

inches

4

4

6

4

mm

102

102

152

102

150, 175, 200, 225, 250

inches

5

5

8

6

mm 127

127

203

152

FIGURE 9 - Concentric Adapter Box Connections for Sizes 300, 350, and 400

Models UDAS and

UDBS 300, 350, and

400 - Pipe Diameters

and Connections

Required at the

Concentric Adapter Box

Requires a 6 to 5 inch (152 to 127mm) taper-type

pipe diameter reducer a maximum of

6” (152mm) from the concentric adapter box.

5” (127mm) diameter vent pipe (Type of pipe

must comply with requirements on page 3.)

8” (203mm)

diameter

single-wall

inlet air pipe

6” (152mm) diameter

single-wall inlet air pipe

attaches to the heater

.

6” (152mm) diameter vent

pipe att

aches to the heater

.

Type of pipe must comply

with requirement

s on p

age 3.

Concentric

Adapter Box

• Sizes 300, 350, and

400

always require

a 6” to 5” (152 to 127

mm) taper-type reducer

in the vent pipe.

This manual is related to the following products: