beautypg.com

Reznor UDBS Option - Installation - Separated Combustion Venting User Manual

Page 11

background image

Form I-UD-V-SC, PN195676R17, Page 11

FIGURE 11 -

Brackets for

Attaching the

Concentric

Adapter Box

to the Wall

1) Attach the Brackets to the Box - The 6” (152mm)

portion of each bracket is designed with five 7/32”

diameter holes so that attachment to the box can

be adjusted.

If the wall is combustible, position brackets to allow for

a 2” (51mm) clearance between the box and the wall.

Adjust bracket attachment to allow for the slight

downward pitch of the terminal vent pipe.

After careful positioning, use sheetmetal screws to

attach the brackets. NOTE: If any holes are made in

the box in error, they must be sealed.

2) Attach the Box to the Wall (Step 5)

When the box is attached to the wall in Step 5, use the

2-1/2” (64mm) portion of the brackets. To adjust to

construction each bracket has three 7/32” diameter holes.

6) On the outside, position the inlet air guard over the

end of the combustion air pipe. See

FIGURE 12, below

and next page. Attach the guard to the inlet air pipe

with the four 1/2” long screws provided.

7) Determine length and install the “terminal-end”

vent pipe.

a. Determine length of pipe. The length of the

continuous piece of terminal-end vent pipe is

determined by the installation within the maximum

and minimum requirements. See

FIGURE 12 to

determine lengths of each segment and calculate the

total length required. The “terminal-end” vent pipe

extending through the box and concentric through the

inlet air pipe

must be one piece of vent pipe without

joints. The connection to the vent pipe run, must be

a maximum of 6” (152mm) from the heater side of the

box.

b. Install terminal-end vent pipe. Being sure the vent

pipe is in the proper flow direction, slide the end

through the box. Position the vent pipe so that it will

extend between 3” (76mm) and 6” (152mm) past the

end of the combustion air pipe and no more than 6”

(152mm) out of the box toward the heater.

No more than 6” (152mm) from the box, connect the

terminal-end vent pipe to the vent pipe run from the

heater.

8) Position the exhaust grill over the end of the vent

pipe. See FIGURE 12, Top View. Attach the grill to the

end of the vent pipe with the four 1/2” long screws in

the kit.

9) Seal the vent pipe to the concentric adapter box.

Verify that the terminal-end section of vent pipe has a

slight downward drop (1/4” per foot/6mm per 305mm)

toward the outside. Use silicone sealant and seal the

circumference of the pipe and the opening of the box.

Seal the area around the pipe completely.

10) Attach the indoor combustion air pipe. Use

sheetmetal screws to attach the single-wall

combustion air pipe run to the collar on the concentric

adapter box. Seal with tape or sealant.
NOTE: If using 3” combustion air pipe on Size 30,

45, or 60, install a taper-type reducer as illustrated in

FIGURE 7, page 7.

Review Paragraph 1.7 concerning condensation;

comply with all requirements that apply.

FIGURE 12 - Installation of a Typical Separated-Combustion Unit with Horizontal Vent

Terminal and Combustion Air Pipe (Option CC6) - continued on page 12

Concentric

Adapter

Box Wid

th

Wall

Exhaust

Grill

Inlet Air

Guard

Combustion Air to Heater (seal joints)

Vent (Flue Exhaust) Pipe

from heater (seal joints)

Heater

Distance between the

Concentric Adapter Box

and the Heater

For Maximum Length, see TABLE 2 on page 4.

Minimum length is 1 ft (.3M) for Sizes 30-75.

Minimum length is 3 ft (.9M) for Sizes 150-400.

Attach one-piece “terminal end” pipe to

vent run no more than 6” (152mm) from

the box.

Attach box to wall with brackets.

One-piece

“Terminal End”

Vent Pipe

Minimum

4” (102mm)

Maximum

16” (406mm)

(152

mm)

1” (25mm) Minimum

48” (1219mm)

Maximum

Minimum

3” (76mm)

Maximum

6” (152mm)

2” (51mm) if wall is combustible

Top

View

This manual is related to the following products: