beautypg.com

0 vertical vent instructions - option cc2 (cont’d) – Reznor UDBS Option - Installation - Separated Combustion Venting User Manual

Page 14

background image

Form I-UD-V-SC, PN195676R17, Page 14

6) Determine the length and install the double-wall vent pipe.

a. Determine minimum length of the continuous section of double-wall vent

pipe. See FIGURE 15. The vent pipe extending through the box and the inlet air

pipe

must be one piece of double-wall vent pipe without joints.

Determine the minimum length by adding the requirements. Starting at the bottom,

the maximum the vent pipe can extend below the box is 6” (152mm);

plus 6”

(152mm) through the box;

plus length of bracket extending above the box; plus

the width of the roof;

plus the height of the outside combustion air pipe above the

roof;

plus a minimum of 3” (76mm) beyond the top of the inlet air pipe. Total is the

minimum length of the vent pipe section. If the actual piece of vent pipe is longer,

extend it further above the combustion air pipe. Do not extend it more than 6”

(152mm) below the box.

FIGURE 15 -

Concentric Adapter

Box, Outdoor

Combustion Air Pipe,

and Concentric Vent

Pipe

Concentric

Adapter Box

Mounting Brackets

X = length of

combustion air pipe required

through and above the roof.

Height from box to top of inlet air

pipe must not exceed 48” (1219mm).

Minimum height above the roof is

18” (457mm) and must be higher

than anticipated snow depth.

First, attach Combustion Air Pipe and install the

Concentric Box

1) Determine length (X) of pipe (see requirements

on the left).

2) Attach the pipe to the collar on the box.

3) Attach the brackets to the roof.

V

ent Flow

22” (559mm) minimum

Cold Climate NOTE:

In geographic areas where

the design ambient is -10°F

or lower, this minimum

height is 34” (864mm).

Collar for Indoor Portion of

the Combustion Air Pipe

Terminal Vent Pipe -

Extend length of vent

pipe a maximum of 6”

(152mm) below the box.

After box is installed, install Concentric Vent Pipe -

One piece of continuous double-wall pipe must

extend from a minimum of 3” (76mm) above the

outer combustion air pipe to a maximum of 6”
(152mm) below the box.
(NOTE: Vent pipe does not
attach to the box; it must be supported
.)

1) Calculate height (see requirements on the left).

2) Be sure vent flow marking on the pipe is in the right

direction.

3) Slide pipe through the box and the outer inlet air pipe.

4) Attach to vent run no more than 6” (152mm) from the

adapter box. See instructions in FIGURE 3, page 5.

Vent pipe

extending

through the

box and the

combustion

air pipe MUST

be one continuous

piece of double-

wall vent pipe.

A second section

of double-wall pipe

is permitted, joining

the long continuous

piece of vent pipe a

minimum of 3” (76mm)

above the top of the

combustion air pipe.

3” (76mm)

minimum

If needed, add a second section of double-wall pipe to

comply with the height requirement on the left.

Terminal V

ent Pipe

(See requirement

s, p

age 3.)

b. Install the vent terminal pipe.

Being sure the pipe is in the proper flow direction, slide

the end into the box and out through the combustion

air pipe. Position the vent pipe so that the end is no

more than 6” (152mm) below the box. The upper

end should extend at least 3” (76mm) above the

combustion air pipe.

NOTE: The vent pipe does

not attach to the box. The installer must provide

support.

Follow the instructions in

FIGURE 3, page 5, for

connecting a double-wall pipe to a single-wall pipe or

taper-type connector.
Seal the circumference of the pipe and the opening of

the box with silicone sealant. Seal the area around the

pipe completely.

7) On the outside, if an additional section of vent pipe is

needed (See

FIGURE 16), add it. Make joint according

to the pipe manufacturer’s requirements. When vent

pipe is the required height,

slide the combustion

air inlet over the vent pipe and fasten the collar to

the combustion air pipe with sheetmetal screws. See

FIGURE 16. Seal the opening at the top between the

vent pipe and the combustion air inlet with silicone

sealant to prevent water leakage.

8) Attach the exhaust (vent) cap. Follow the illustrated

instructions in

FIGURE 2, page 5.

3.0 VERTICAL VENT INSTRUCTIONS - Option CC2 (cont’d)

3.2 Installation Instructions for Vertical Vent/Combustion Air Kit Option CC2 (cont’

d)

This manual is related to the following products: