Form I-UD-V-SC, PN195676R17, Page 5

Applies to: Residential or Commercial/Industrial Installation

NOTE: Only UDAS 30, 45, 60, 75, 100, and 125 are certified for residential use.

FIGURE 2 - Follow STEPS to join Double-Wall (Type B) Pipe and the Vent Terminal Cap

(applies only to vertical vent/combustion air kit Option CC2)

FIGURE 2 - STEP 1

Place a continual 3/8” bead of silicone sealant

around the circumference of the vent cap

collar. This will prevent any water inside the

vent cap from running down the double-wall

pipe.

FIGURE 2 - STEP 2

Insert the collar on the vent cap inside

the inner wall of the double-wall pipe.

Insert as far as possible. Add additional

silicone sealant to fully close any gaps

between the vent cap and the double

wall pipe. This is necessary to prevent

water from entering the double-wall pipe.

Secure the vent cap to the double-wall

pipe by drilling and inserting

a 3/4” (19mm) long sheetmetal screw

into the vent cap collar.

Do not overtighten screw.

FIGURE 2 - STEP 3

FIGURE 3 - Follow STEPS to join Double-Wall (Type B) Pipe to a Single-Wall Vent Pipe Run

(NOTE: Comply with pipe requirements on page 3.)

Do STEP 2

immediately

following

STEP 1.

FIGURE 3 - STEP 1

On the single-wall pipe or

taper-type connector, place

a continual 1/4” bead of

silicone sealant around the

circumference.
Do STEP 2 immediately

following STEP 1.

FIGURE 3 - STEP 2

Insert the pipe prepared with sealant

into the inner pipe of the double-

wall pipe until the bead of sealant

contacts the inner pipe creating a

sealed joint.

FIGURE 3 - STEP 3

Spaced equally around the double-wall

pipe, drill three small holes below the

sealant ring. Insert 3/4 inch (19mm) long

sheetmetal screws to secure the joint. Do

not overtighten screws.

Double-

Wall Pipe

Single-Wall Pipe with

Sealant (STEP 1)

1.5 Support

Support horizontal run every six feet (1.8M).
Support vertical run of Category III vent pipe in accordance with the requirements of

the pipe manufacturer.
Support vertical single-wall pipe in accordance with accepted industry practices.
Do not rely on the heater or the adapter box for support of either horizontal or vertical

pipes. Use non-combustible supports on vent pipe.
NOTE: The vertical vent terminal pipe does not attach to the concentric adapter box

and must be supported during installation.

1.6 Clearance

Do not enclose the vent pipe or place pipe closer than 6” (152mm) to combustible

material.