Applies to: Residential or Commercial/Industrial Installation

NOTE: Only UDAS 30, 45, 60, 75, 100, and 125 are certified for residential use.

Diameters of the

outside (terminal) concentric pipes are listed in TABLE 3.

1.3 Pipe Diameter and

Length

Pipe diameter and length requirements listed in

TABLE 2 are for the indoor sections

of pipe between the heater and the concentric adapter box.
Pipe diameters and maximum indoor vent lengths in

TABLE 2 apply to both horizon-

tal and vertical vent/combustion air systems. Add all straight sections and equivalent

lengths for elbows.

The total length of the straight sections and elbows must not

exceed the Maximum Length.

TABLE 2 - Pipe

Diameter and Length

from Heater to

Concentric Adapter

Box

• Minimum length

between the heater and

the concentric adapter

box is 1 ft (305mm)

for Sizes 30-125 and

3 ft (914mm) for Sizes

150-400.

1.4 Joints and Sealing

Provide pipes as specified in

Requirement No. 1.1, page 3, and seal joints as follows:

• To join sections of Category III pipe, follow the pipe manufacturer’s instructions

for joining and sealing.

• To join sections of single-wall pipe (vent pipe or combustion air pipe), secure

slip-fit pipe connections using sheetmetal screws or rivets. Seal all joints with

aluminum tape or silicone sealant.

• When joining the terminal section of double-wall vent pipe (vertical vent

terminal Option CC2 only) to the vent cap, follow the illustrated step-by-step

instructions in

FIGURE 2.

When joining a terminal section of double-wall vent pipe to a single-wall a

vent pipe run, follow the illustrated step-by-step instructions in FIGURE 3.

When joining two sections of double-wall vent pipe, follow the pipe

manufacturer’s instructions for joining and sealing vent pipe sections.

NOTE: Joints connecting

double-wall pipe apply

only to a vertical vent

terminal (Option CC2

Vertical Vent/Combustion

Air Kit). See Type of Pipe

requirement on page 3.

UDAS and UDBS

30, 45, 60, 75, 100, 125

150, 175, 200, 225, 250, 300, 350, 400

Inlet Air Pipe Diameter

6” (152mm)

8” (203mm)

Vent Pipe Diameter

4” (102mm)

5” (127mm)

Pipe Diameter and Maximum Length from Heater to Concentric Adapter Box

UDAS

and

UDBS

Pipe Diameter

Maximum

Length

Equivalent Straight Length for a

Vent Pipe Inlet Air Pipe

90° Elbow

45° Elbow

inches mm inches mm

feet

M

feet

M

feet

M

30

3

76

3

76

15

4.6

2

0.6

1

0.3

4

102

4

102

10

3.0

2

0.6

1

0.3

45

3

76

3

76

15

4.6

2

0.6

1

0.3

4

102

4

102

10

3.0

2

0.6

1

0.3

60

3

76

3

76

25

7.6

3

0.9

1.5

0.5

4

102

4

102

15

4.6

1.5

0.5

1

0.3

75

4

102

4

102

25

7.6

3

0.9

1.5

0.5

100

4

102

4

102

35 10.7

4

1.2

2

0.6

125

4

102

4

102

35 10.7

4

1.2

2

0.6

150

5

127

6

152

30

9.1

3

0.9

1.5

0.5

175

5

127

6

152

30

9.1

3

0.9

2

0.5

200

5

127

6

152

40 12.2

4

1.2

2

0.6

225

5

127

6

152

40 12.2

4

1.2

2

0.6

250

5

127

6

152

40 12.2

4

1.2

2

0.6

300

6

152

6

152

45 13.7

4

1.2

2

0.6

350

6

152

6

152

45 13.7

5

1.5

2.5

0.8

400

6

152

6

152

45 13.7

5

1.5

2.5

0.8

The outdoor pipe lengths depend on the installation; requirements are listed in the installation instructions for the hori-

zontal (Option CC6) and vertical (Option CC2) vent/combustion air kits.

TABLE 3 - Diameters

of Concentric (outdoor)

Pipes

1.0 Venting and Combustion Air Requirements (cont’d)

This manual is related to the following products: