beautypg.com

2 troubleshooting guide, 0 maintenance and service (cont'd) – Reznor RIHVL Unit Installation Manual User Manual

Page 18

background image

11.0 Maintenance and Service (cont'd)

11.2 Troubleshooting Guide

SYMPTOM

POSSIBLE CAUSE

CORRECTIVE ACTION

Gas Odor

1. Gas pipe joints loose.

1. Check joints with non-corrosive leak detection

fluid, tighten as needed.

New Installation

of heaters not

working

1. Heaters not isolated during high pressure leak testing

of gas lines

1. Replace combination gas valve(s) on each heater.

2. All gas lines not completely bled of air

2. Disconnect flex hose at each heater until gas is

present. Connect flex hose and leak test.

3. Gas supply regulator reversed

3. Remove and install properly.

4. Electrical supply line voltage & neutral polarity reversed 4. Correct electrical supply polarity.

No gas

1. Gas supply valves not opened

1. Open all manual gas supply valves.

2. Gas supply regulator sticking

2. Replace gas supply regulator.

Electrical

circuit closed

but heater not

working. (For

specific control

systems see

Ignition and

Operation

section)

1. Gas supply lacking caused control system lockout

1. Verify all gas supply valves are open. Purge air

from gas supply line. Turn thermostat off – wait 5

minutes, then reset thermostat.

2. Line fuse blown or tripped circuit breaker

2. Replace line fuse or reset breaker.

3. Electrical power short

3. Trace and correct short.

4. Wiring disconnected

4. Repair, see wiring diagram in Ignition section.

5. No electrical earth ground

5. Provide electrical earth ground.

6. Electrical supply line voltage & neutral polarity reversed 6. Correct electrical supply polarity.

7. Exhaust fan interlock (if used) is defective

7. Replace interlock.

Direct spark

fails to ignite

main burner(s)

1. Combination gas valve not in the ON position

1. Turn combination gas valve to ON position.

2. Electrode wire loose

2. Reconnect wire.

3. Electrode wire broken or frayed

3. Replace electrode.

4. Electrode ceramic cracked

4. Replace electrode.

5. Electrode improperly located

5. Relocate to correct position.

6. Gas valve fails to open when power is applied

6. Replace combination gas valve.

7. Supply/manifold gas pressure too low

7. See rating plate on heater and adjust pressure.

8. Ignition detection control defective

8. Replace ignition detection control.

Unit cycles on

and off, erratic

operation

1. Drafty condition

1. Shield heater and/or thermostat from drafts.

2. Flame sensor wire loose or damaged

2. Replace wire harness to ignition detection control.

3. No electrical earth ground

3. Provide electrical earth ground.

4. Electrical supply line voltage & neutral polarity reversed 4. Correct electrical supply polarity.

5. Heat on pilot flame sensor insufficient

5. Clean pilot, check pilot orifice and alignment.

No pilot

1. Gas line contains air

1. Purge air from gas line.

2. Pilot line, orifice, or passage blocked

2. Check and clean. See Paragraph 11.1.

3. Pilot solenoid valve inoperative

3. Replace combination gas valve.

Pilot goes out

on 100% shut-

off when hold-

down button is

released

1. Heat on pilot flame sensor insufficient

1. Clean pilot, check pilot orifice and alignment.

2. Pilot flame sensor location improper

2. Correct position with respect to pilot.

3. Manifold gas pressure low

3. See rating plate on heater and adjust pressure.

4. Poor contact at valve end of sensing element

4. Ensure clean and proper contact.

5. Pilot flame sensor defective

5. Replace pilot flame sensor.

6. Pilot interrupter in combination gas valve defective

6. Replace combination gas valve

Pilot burning,

no gas to main

burner(s)

1. Thermostat or manual switch open

1. Raise the thermostat setting or close switch.

2. Manual valve closed on combination gas valve

2. Turn valve to “ON” position.

3. No power to solenoid in combination gas valve

3. Check power supply and furnish proper voltage.

4. Heat on pilot flame sensor insufficient

4. Clean pilot, check pilot orifice, and alignment.

5. Pilot flame sensor defective

5. Replace sensor.

6. Combination gas valve defective

6. Replace combination gas valve.

Heater will not

turn off

1. Thermostat defective

1. Replace thermostat.

Controls over-

heating

1. Heater mounted incorrectly

1. See Location, Paragraph 2.0, and Suspending,

Paragraph 5.

Burning of gas

inside burner

(flash-back)

1. Heater mounted incorrectly

1. See Location, Paragraph 2.0, and Suspending,

Paragraph 5.

2. Gas leaking from: manifold, control assembly, or pilot

joints causing gas ignition at orifice

2. Check joints with non-corrosive leak detection

fluid, tighten as needed.

3. Ceramic tile(s) cracked or separating

3. Replace burner.

4. Drafts excessive

4. Shield from drafts or relocate heater.

Carbon forma-

tion on ceramic

surface or

burner

1. Gas supplied is wrong type

1. Check rating plate for type of gas required.

2. Venturi obstructed (by spider web)

2. Clean with a bottle brush.

3. Pilot depositing carbon

3. Clean pilot and check pilot orifice.

4. Supply/manifold gas pressure too low

4. See rating plate on heater and adjust pressure.

5. Main gas orifice(s) misaligned

5. Consult sales agent or factory

P/N 131793R10, Page 18