beautypg.com

0 mechanical (cont'd), 1 unit inlet air (cont'd), 3 optional dampers and damper controls – Reznor RBL (Cabinet Blower) Unit Installation Manual User Manual

Page 6: 2 outside air hoods (cont'd)

background image

Form I-RBL, P/N163219R2, Page 6

Top Panel (edge must be

underneath cabinet top)

Left Side

Panel

Right Side

Panel

Factory-assembled

Louver Assembly

including Moisture

Eliminating Louvers

and Screen

Bottom

Panel

FIGURE 7B - Assembly

Drawing of Option AS2

Outside Air hood

FIGURE 7A - Dimensions of Optional

Outside Air Hood

(NOTE: The width of the outside air hood is the same

as the width of the blower cabinet.)

Optional 100%

Outside Air Hood

43-17/32” (1106mm)

4-5/8”

(117mm)

31-11/32”

(796mm)

14” (356mm)

minimum

Screened Inlet Air Hood for 30% Outside Air Opening, Part of Inlet

Air Options AR6 and AR7) -The assembled outside air hood included

in the air inlet options that have a 30% outside air opening (Option AR6

or AR7) is shipped separately for field installation.

Installation Instructions - 30% Outside Air Hood

1. On the inlet air side of the blower cabinet, remove the factory

installed screws attaching the blower cabinet top.

2. Slide the air hood top flange underneath the lip of the blower cabi-

net top and the sides into the vertical slots. The air hood flange

must be between the blower cabinet top and the cabinet end panel.

3. Reinsert all of the sheetmetal screws.

Blower

Cabinet

Remove two corner

and complete row

of screws

Slide top

flange

underneath

the cabinet

top

Vertical Slots -

Slide side flanges

into slots

30% Outside

Air Hood

Width of

Outside

Air Hood
58-7/8"
1495mm

5.0 Mechanical

(cont'd)

5.1 Unit Inlet Air

(cont'd)

1) Damper Motor

2) Return Air Damper

3) Potentiometer

4) Potentiometer

5) Mixed Air Controller

6) Warm-up Control

7) Outside Air Damper

8) Damper Motor Transformer

7

8

1

2

3 4 5 6

9

FIGURE 9 - Location of Controls

for 30% Outside Air Hood

(FIGURE 8) and Damper Option

AR6 or AR7

FIGURE 10 - Control

Locations for 100%

Outside Air and 100%

Return Air Damper

Options

Blower

30% Outside

Air Damper

30% Outside

Air Hood

Damper Motor

Optional

Bottom

Return Air

5.1.3 Optional Dampers and Damper Controls

NOTE: The illustrations in FIGURES 9 & 10 are intended to show location only of various air control accessories and

do not represent suggested combinations of accessories.

Attach the support angle to the air hood bottom panel. The bottom panel of the

air hood and the support angle should be tight together; do not draw with the

sheetmetal screws.

4. Louver Assembly -- With the intake screen toward the inside of the hood, posi-

tion the pre-assembled vertical louver assembly in the inlet opening of the air

hood. Using the remaining sheetmetal screws, attach the louver assembly to the

air hood side panels using the holes provided.

5.1.2 Outside Air Hoods (cont'd)

FIGURE 8 - Installation of Air Hood with 30% Outside Air Opening Option