beautypg.com

0 commissioning and start-up – Reznor RBL (Cabinet Blower) Unit Installation Manual User Manual

Page 11

background image

Form I-RBL, P/N163219R2, Page 11

Voltage

/Phase

Motor

HP

Wire

Gauge

BX

Cable

208/1 or

230/1

1 - 2

14

3/8"

3

10

1/2"

5

8

1/2"

7.5

6

1"

10

4

1"

208/3 or

230/3

1 - 4

14

3/8"

5

12

3/8"

7.5

10

1/2"

10

8

1/2"

15

6

1"

20

4

1"

460/3

1 - 7-1/2

14

3/8"

10

12

3/8"

15

10

1/2"

20

8

1/2"

575/3

1 - 7-1/2

14

3/8"

10 - 20

10

1/2"

Field-supplied Wiring

Size from Disconnect

to Electrical Box for

Connection to Motor

Contactor or Starter

Disconnect Switch

-

A disconnect switch is a

required part of this installation. Switches are

available, as options or parts, or may be pur-

chased locally. When ordered as an optional

component, the disconnect switch is shipped

separately.

The disconnect switch may be fusible or non-fus-

ible. When installing, be careful that the conduit

and switch housing are clear of cabinet panels.

Allow at least four feet (1.2M) of service room

between the switch and removable panels.
Convenience Outlet Option - When a conve-

nience outlet (Option BC) is included, a separate

power supply must be provided to the receptacle.

This circuit MUST BE on a ground fault breaker to

meet requirements. All wiring to the convenience

outlet must meet National Electrical Code ANSI/

NFPA No. 70 (latest edition) and any local or util-

ity codes that apply.

Control Wiring

Field Control Wiring - Length and Gauge

Total Wire Length

Distance from Unit to Control

Minimum Recommended Wire Gauge

150 ft (46M)

75 ft (23M)

#18 gauge

250 ft (76M)

125 ft (38M)

#16 gauge

350 ft (107M)

175 ft (53M)

#14 gauge

1

2

3

5 4

6

7

8

9

10

11

12

13

1415 16

18 19

17

FIGURE 16 - Location of Electrical Connections and

Standard and Optional Controls

(Illustration is not an RBL cabinet but controls are in same location

in a Model RBL.)

1) Line Voltage Connection (field)

2) Optional Convenience Outlet

3) Blower Motor Contactor or Starter

4) Optional Outside Air or Return Air

Controller

5) Optional Mixed Air Controller

6) Optional Potentiometer

7) Optional Potentiometer

8) Optional Return Air Dampers

9) Optional Filters

10) Optional Two-Position or

Modulating Damper Motor

11) Optional Outside Air Dampers

12) Blower Motor (Drive on opposite

Side) - Available in Open, TEFC,

Energy Efficient or Two-Speed

13) Optional Control Relays (as

required - 8 maximum)

14) Low Voltage Terminal Strip

15) Line Voltage Terminal Strip

16) Control Transformer

17) Control Transformer (as

required)

18) Optional Damper Motor

Transformer

19) Low Voltage Connection (field)

7.0 Commissioning

and Start-Up

Be certain electrical supply matches voltage rating on unit (see rating plate).

Check all field wiring against wiring diagram. Be sure wire gauges are as required

for the electrical load. This information appears on the wiring diagram.

Be certain that electrical entries are sealed against the weather.

See that fuses or circuit breakers are in place and sized correctly.

Check blower pulley and motor pulley to be sure they are secure to shafts. Check

belt tension; see Paragraph 5.3.

If the unit is equipped with outside air and return air dampers, adjust the damper

linkage. See Paragraph 5.1.3.

Close all panels tightly.

Return this book to the "Owner's Envelope" for future reference.

Check the wiring diagram and literature supplied with the cabinet for operation of fac-

tory-installed optional controls. See

FIGURE 16 for location of electrical connections

and available standard and optional controls.