1.8 Technical Details -

Table 5b (VCT)

No of Injectors

1

Gas Connection

½” N.P.T

Electrical Supply

120 volt 1 phase 60Hz

Vent size (in)

4” or 6” (101mm or 152mm)

Unitary Fan Motor Details

120 volt 1 phase 60Hz

Current Rating

1.2A MAX

Ignition

Electronic Program Start up with Spark Ignition

Thermostat

24Vac 60Hz 1.5A Max. total load

MODEL

Natural Gas

LP Gas

Min. Heater

Length

Max. Heater

Length

Min. Heater

Length

Max. Heater

Length

High / Low

Rate BTU/Hr

High / Low

Rate BTU/Hr

S ft (m)

S ft (m)

U (ft)

U (ft)

60

60,000/45,000

60,000/45,000

20 (6.1)

40 (12.1)

20 (6.1)

40 (12.1)

80

80,000/60,000

80,000/60,000

30 (9.1)

40 (12.1)

40 (12.1)

40 (12.1)

100

100,000/65,000

100,000/65,000

30 (9.1)

40 (12.1)

40 (12.1)

40 (12.1)

125

123,500/95,000

125,000/95,000

30 (9.1)

50 (15.2)

40 (12.1)

40 (12.1)

150

150,000/100,000 150,000/100,000

40 (12.1)

60 (18.3)

40 (12.1)

60 (18.3)

170

169,000/125,000 169,000/125,000

50 (15.2)

70 (21.3)

60 (18.3)

60 (18.3)

200

200,000/150,000

N/A

50 (15.2)

70 (21.3)

60 (18.3)

60 (18.3)

N/A

Appliances can be installed up to 10,000 ft in the USA. Altitude conversion kits are available on request.

Natural Gas 0- 2000 ft (0-610m)

USA

Size

60 80 100 125 150 170 200

“WC Hi

4.2 3.9 4.9 4.5

4.4

4.0 3.5

“WC Lo

2.4 2.3 2.1 2.7

2.2

2.4 2.2

LP Gas 0- 2000 ft (0-610m)

USA

Size

60 80 100 125 150 170 200

“WC Hi

6.1 5.2 8.2 7.6

7.2 6.8 N/A

“WC Lo

3.5 3.0 3.7 4.4

3.3 3.9 N/A

Natural Gas 2001- 4000 ft (611-1220m)

USA

Size

60

80 100 125 150 170 200

“WC Hi

4.1 3.7 4.7

4.3

4.2

3.8

3.3

“WC Lo 2.3 2.1 2.0 2.5 2.0 2.2 2.0

USA

LP Gas 2001- 4000 ft (611-1220m)

Size

60 80 100 125 150 170 200

“WC Hi

6.0 5.0 8.0 7.4 7.0

N/A

“WC Lo

3.4 2.9 3.5 4.2 3.1

N/A

Natural Gas 0- 2000 ft (0-610m)

CANADA

Size

60 80 100 125 150 170 200

“WC Hi

4.2 3.9 4.9 4.5 4.4

4.0

3.5

“WC Lo

2.4 2.3 2.1 2.7 2.2

2.4

2.2

LP Gas 0- 2000 ft (0-610m)

CANADA

Size

60

80 100 125 150 170 200

“WC Hi

6.1 5.2 8.2 7.6 7.2 6.8 N/A

“WC Lo

3.5 3.0 3.7 4.4 3.3 3.9 N/A

Natural Gas 2001- 4500 ft (611-1370m)

CANADA

Size

60 80 100 125 150 170 200

“WC Hi

4.1 3.7 4.7 4.3 4.2

3.8

3.3

“WC Lo

2.3 2.1 2.0 2.5 2.0

2.2

2.0

CANADA

LP Gas 2001- 4500 ft (611-1370m)

Size

60 80 100 125 150 170 200

“WC Hi

6.0 5.0 8.0 7.4 7.0

N/A

“WC Lo

3.4 2.9 3.5 4.2 3.1

N/A