12

cap with bird screen must be fitted at
the inlet of the duct. If the duct inlet
is located above the roof the
underside of the inlet terminal must
be at least 2ft (0.61m) above roof
level and at least 10” (254mm)
above any projection on the roof
within 7ft (2.1m) of the inlet. Intake
pipe, fittings and sealant are not
furnished by the manufacturer. Refer
fig 8c & 8d

Figure 8.a Vertical Venting.

Figure 8.b Horizontal Venting.

Figure 8.c Fresh Air Ducted Intake.

Figure 8.d Wall Terminal Intake Kit.

REFLECTOR

END OF RADIANT TUBE

VENT ADAPTOR ELBOW

12'-0" (3.66m)

12'-0" (3.66m)

(APPROXIMATE

MAXIMUM DIMENSIONS)

CODE APPROVED VENT
THROUGH ROOF

SEAL

S

UP

PL

IE

D B

Y

OTHERS

ROOF

4" (101mm) O.D. OR

HIGH TEMPERATURE SILICONE

SEAL JOINTS WITH

REQUIRED ONLY FOR 6" (152mm) DIA. VENT

4" (101mm) TO 6" (152mm) DIA. ALUMINUM ADAPTER

6" (152mm) O.D. FLUE

ALUMINUM

RADIANT
TUBE

REFLECTOR

4" (101mm) TO 6" (152mm) DIA. ALUMINUM ADAPTER

TERMINAL

6" (152mm)

COLLAR

SEAL JOINTS WITH

HIGH TEMPERATURE

WALL

REQUIRED ONLY FOR 6" (152mm) DIA. VENTS

ALUMINUM 4" (101mm) O.D. MAXIMUM LENGTH = 12'-0" (3.66m)
ALUMINUM 6" (152mm) O.D.MAXIMUM LENGTH = 25'-0" (7.62m)
(PLUS A MAXIMUM OF 2 x 90° BENDS

END OF

SUPPLIED BY OTHERS

COUPLER

SILICONE

INLET WITH
BIRD SCREEN

36"

(91

4mm) MIN CENT

ER

S

NOTE: The vent
terminal should be
installed so as to be in
the same atmospheric
pressure zone as the
combustion air inlet of
the appliance

INLET WITH

6" (152mm)

SEAL JOINTS WITH

SILICONE OR DUCT TAPE

WALL

BIRD SCREEN

TERMINAL

36" (914m

m) MIN CENTERS

CLAMPS

BURNER

4" (106mm) O.D. FLEXIBLE DUCT

ALUMINUM 4" (101mm) O.D. PIPE

MAX LENGTH = 25'-0" (7.62m) WITH 2-90° LONG RADIUS BENDS

4.25” (108mm) O.D FLEXIBLE DUCT

ENSURE ALL JOINTS ARE

SEALED

APPROVED CAT III VENT PIPE

APPROVED CAT 3 VENT PIPE

VENT CAT III ELBOW

ELBOWS

CAT III ADAPTER

ELBOWS